[sc_sw authority and mode in info routing, 1, en_US]
Figure 8-33
Display of Switching Authority and Switching Mode in the Information Routing (in Function
Block General), Example of 2 Activated Remote Switching Authorities
Individual Switching Authority and Switching Mode for the Switching Devices
In a standard case, the functionalities switching authority, switching mode, and specific switching authority as
described in the previous sections, are applicable to the entire bay unit and, therefore, are valid for all
switching devices that are controlled by this bay unit. In addition, you can configure an individual switching
authority and specific switching authority as well as individual switching modes for single switching devices.
Therefore, individual switching devices can accept various switching authorities and switching modes simulta-
neously.
This is offered for the following function groups and function blocks:
Circuit-breaker function group
Disconnector function group
Transformer tap changer function group
Switching sequence function block
This allows to select individual settings for each switching device. This is useful if, for example, switching
devices of different utilities are managed within a single bay.
In order to activate this option, go to the function block Control of a switching device and set the parameter
Check switching authority to advanced. An additional table containing initially 2 parameters is
displayed.
Control Functions
8.3 Control Functionality
1114 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017