Addr. Parameter C Setting Options Default Setting
_:16351:162 90V V.contr.gc:Power-
flow supervision
•
off
•
on
on
_:16351:163 90V V.contr.gc:Regulate
with T2 at start
•
off
•
on
on
_:16351:171 90V V.contr.gc:Set point
mode active
•
off
•
on
on
Line drop comp.
_:16351:125 90V V.contr.gc:Line drop
compensation
•
off
•
LDC-Z
•
LDC-XandR
off
_:16351:126 90V V.contr.gc:Target
voltage rising w1
0.0 % to 20.0 % 4.0 %
_:16351:147 90V V.contr.gc:Target
voltage rising w2
0.0 % to 20.0 % 4.0 %
_:16351:127 90V V.contr.gc:Max load
current
0.0 % to 500.0 % 100.0 %
_:16351:153 90V V.contr.gc:R line w1 0.0 Ω to 30.0 Ω 0.0 Ω
_:16351:154 90V V.contr.gc:X line w1 -30.0 Ω to 30.0 Ω 0.0 Ω
_:16351:155 90V V.contr.gc:R line w2 0.0 Ω to 30.0 Ω 0.0 Ω
_:16351:156 90V V.contr.gc:X line w2 -30.0 Ω to 30.0 Ω 0.0 Ω
Limiting
_:16351:102 90V V.contr.gc:Lower
tap-position limit
-128 to 127 1
_:16351:103 90V V.contr.gc:Higher
tap-position limit
-128 to 127 15
_:16351:128 90V V.contr.gc:Vmin
limiting
•
off
•
on
on
_:16351:129 90V V.contr.gc:Vmin
threshold w1
10.000 V to 340.000 V 105.000 V
_:16351:148 90V V.contr.gc:Vmin
threshold w2
10.000 V to 340.000 V 105.000 V
_:16351:130 90V V.contr.gc:Vmin
time delay
0 s to 20 s 10 s
_:16351:131 90V V.contr.gc:Vmax
limiting
•
off
•
on
on
_:16351:132 90V V.contr.gc:Vmax
threshold w1
10.000 V to 340.000 V 115.000 V
_:16351:149 90V V.contr.gc:Vmax
threshold w2
10.000 V to 340.000 V 115.000 V
_:16351:133 90V V.contr.gc:Vmax
time delay
0 s to 20 s 10 s
Blocking
_:16351:134 90V V.contr.gc:Blocking
behavior
•
Auto
•
Auto-Manual
Auto-Manual
_:16351:135 90V V.contr.gc:V<
Blocking
•
off
•
on
on
_:16351:136 90V V.contr.gc:V<
Threshold w1
10.000 V to 340.000 V 90.000 V
_:16351:150 90V V.contr.gc:V<
Threshold w2
10.000 V to 340.000 V 90.000 V
Control Functions
8.9 Voltage Controller
1230 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017