Integrated Power Supply
Auxiliary rated voltage V
H
(PS201, PS203, CB202)
DC 24 V/DC 48 V DC 60 V/DC 110 V/DC 125 V/DC 220 V/
DC 250 V or
AC 100 V/AC 115 V/AC 230 V, 50 Hz/60 Hz
Permissible voltage
ranges (PS101)
Only for non-modular
devices
DC 19 V to DC 60 V DC 48 V to 150 V DC 88 V to DC 300 V
AC 80 V to AC 265 V,
50 Hz/60 Hz
Auxiliary rated voltage V
H
(PS101)
Only for non-modular
devices
DC 24 V/DC 48 V DC 60 V/DC 110 V/
DC 125 V
DC 110 V/ DC 125 V/
DC 220 V/DC 250 V
or
AC 100 V/AC 115 V/
AC 230 V, 50 Hz/60 Hz
Superimposed alternating
voltage, peak-to-peak,
IEC 60255-11
≤ 15 % of the DC auxiliary rated voltage (applies only to direct voltage)
Inrush current ≤ 18 A
Recommended external
protection
Miniature circuit breaker 6 A, characteristic C according to IEC 60898
Internal fuse
DC 24 V to DC 48 V DC 60 V to DC 125 V DC 24 V to DC 48 V
AC 100 V to AC 230 V
PS101
Only for non-modular
devices
4 A inert, AC 250 V,
DC 150 V,
UL recognized
SIBA type 179200 or
Schurter type SPT 5x20
2 A time-lag, AC 250 V, DC 300 V, UL recognized
SIBA type 179200 or Schurter type SPT 5x20
PS201, PS203, CB202 2 A time-lag, AC 250 V, DC 300 V, UL recognized
SIBA type 179200 or Schurter type SPT 5x20
Power consumption (life relay active)
DC AC 230 V/50 Hz AC 115 V/50 Hz
1/3 base module, non-
modular
Without plug-in modules
7.0 W 16 VA 12.5 VA
1/3 base module, modular
Without plug-in modules
13 W 33 VA 24 VA
1/6 expansion module 3 W 6 VA 6 VA
1/6 plug-in module
assembly without plug-in
modules (modules CB202)
3.5 W 14 VA 7 VA
Plug-in module for base
module or plug-in module
assembly (for example,
communication module)
< 5 W < 6 VA < 6 VA
Stored-energy time for auxiliary voltage outage or
short circuit, modular devices
For V ≥ DC 24 V ≥ 50 ms
For V ≥ DC 110 V ≥ 50 ms
For V ≥ AC 115 V ≥ 50 ms
Stored-energy time for auxiliary voltage outage or
short circuit, non-modular devices
For V ≥ DC 24 V ≥ 20 ms
For V ≥ DC 60 V/DC 110 V ≥ 50 ms
For V ≥ AC 115 V ≥ 200 ms
Technical Data
12.1 General Device Data
1410 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017

Table of Contents

Related product manuals