[scfragew_8, 1, en_US]
Figure 3-99
Query after Changing the Transformer Data (Setting View: Secondary)
If you answer the question with Yes, then DIGSI 5 will recalculate the pickup values (threshold values) in the
active secondary view. For the new secondary transformer current 5 A, the new secondary threshold value
obtained is 7.5 A (1.5 A * 5 = 7.5 A). The primary and percent values remain unchanged.
The following figure shows the newly calculated threshold value in the secondary view.
System Functions
3.9 General Notes for Setting the Threshold Value of Protection Functions
SIPROTEC 5, Overcurrent Protection, Manual 177
C53000-G5040-C017-8, Edition 07.2017