EasyManua.ls Logo

Siemens 7SJ85 - Page 251

Siemens 7SJ85
1638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
[scauser5-220114-01-DE, 1, en_US]
Figure 5-45 Making the Communication Settings
With the selection of the SUP protocol for the 20-mA unit DIGSI automatically adds the function group Analog
units to your device configuration. You can now instantiate the function 20-mA unit serial 1 (see following
figure).
[sc20ser6-220114-01-DE, 1, en_US]
Figure 5-46 Insertion of the Function 20-mA Unit Serial 1
Now, set the channel number over which the SUP protocol runs. In addition, set the slave address of the 20-
mA unit. This address must be set with the same value in the 20-mA unit (refer to the following figure).
For the first use of the 20-mA unit, the following device configuration must be set on the 20-mA unit:
Bus protocol: mod
Device address: 1
Baud rate: 9600
Parity: no
Function-Group Types
5.6 Function-Group Type Analog Units
SIPROTEC 5, Overcurrent Protection, Manual 251
C53000-G5040-C017-8, Edition 07.2017

Table of Contents

Related product manuals