EasyManua.ls Logo

Siemens 7SJ85 - Page 258

Siemens 7SJ85
1638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
[dw_measured-value-scaling, 1, en_US]
Figure 5-55
Scaling Principle
Setting Example 1:
A measuring transducer transmitting a current signal of 4 mA to 20 mA is used as a transmitter. Currents well
below 4 mA indicate a transmitter failure; currents around 0 mA indicate a broken wire. A sensor detecting a
temperature is attached to the transmitter. The upper value corresponds to 200 °C and the lower value to -100
°C. This results in the following characteristic. In accordance with the set characteristic curve, the function
calculates the sensor value from the measured current. The coefficients of the linear equation (gradient and
foot point) are calculated from the set threshold and the sensor values are determined. A supplied current of
9.333 mA corresponds to a temperature of 0 °C.
Function-Group Types
5.6 Function-Group Type Analog Units
258 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017

Table of Contents

Related product manuals