Addr. Parameter C Setting Options Default Setting
_:661:3 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:661:4 Definite-T 1:Dropout
ratio
0.90 to 0.99 0.95
_:661:102 Definite-T 1:Pickup delay 0.00 s to 60.00 s 0.00 s
_:661:101 Definite-T 1:Dropout
delay
0.00 s to 60.00 s 0.00 s
_:661:6 Definite-T 1:Operate
delay
0.00 s to 60.00 s 0.30 s
Dyn.s: AR off/n.rdy
_:661:28 Definite-T 1:Effect. by AR
off/n.ready
•
no
•
yes
no
_:661:35 Definite-T 1:Stage
blocked
•
no
•
yes
no
Dyn.set: AR cycle 1
_:661:29 Definite-T 1:Effected by
AR cycle 1
•
no
•
yes
no
_:661:36 Definite-T 1:Stage
blocked
•
no
•
yes
no
_:661:14 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:661:20 Definite-T 1:Operate
delay
0.00 s to 60.00 s 0.30 s
Dyn.set: AR cycle 2
_:661:30 Definite-T 1:Effected by
AR cycle 2
•
no
•
yes
no
_:661:37 Definite-T 1:Stage
blocked
•
no
•
yes
no
_:661:15 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:661:21 Definite-T 1:Operate
delay
0.00 s to 60.00 s 0.30 s
Dyn.set: AR cycle 3
_:661:31 Definite-T 1:Effected by
AR cycle 3
•
no
•
yes
no
_:661:38 Definite-T 1:Stage
blocked
•
no
•
yes
no
Protection and Automation Functions
6.3 Overcurrent Protection, Phases
336 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017