Addr. Parameter C Setting Options Default Setting
Dyn.s: AR off/n.rdy
_:691:28 Inverse-T 1:Effect. by AR
off/n.ready
•
no
•
yes
no
_:691:35 Inverse-T 1:Stage
blocked
•
no
•
yes
no
Dyn.set: AR cycle 1
_:691:29 Inverse-T 1:Effected by
AR cycle 1
•
no
•
yes
no
_:691:36 Inverse-T 1:Stage
blocked
•
no
•
yes
no
_:691:14 Inverse-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:691:102 Inverse-T 1:Time dial 0.00 to 15.00 1.00
Dyn.set: AR cycle 2
_:691:30 Inverse-T 1:Effected by
AR cycle 2
•
no
•
yes
no
_:691:37 Inverse-T 1:Stage
blocked
•
no
•
yes
no
_:691:15 Inverse-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:691:103 Inverse-T 1:Time dial 0.00 to 15.00 1.00
Dyn.set: AR cycle 3
_:691:31 Inverse-T 1:Effected by
AR cycle 3
•
no
•
yes
no
_:691:38 Inverse-T 1:Stage
blocked
•
no
•
yes
no
_:691:16 Inverse-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:691:104 Inverse-T 1:Time dial 0.00 to 15.00 1.00
Dyn.s: AR cycle>3
_:691:32 Inverse-T 1:Effected by
AR cycle gr. 3
•
no
•
yes
no
_:691:39 Inverse-T 1:Stage
blocked
•
no
•
yes
no
Protection and Automation Functions
6.3 Overcurrent Protection, Phases
SIPROTEC 5, Overcurrent Protection, Manual 347
C53000-G5040-C017-8, Edition 07.2017