Addr. Parameter C Setting Options Default Setting
_:27 User curve #:Blk. w.
inrush curr. detect.
•
no
•
yes
no
_:3 User curve #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:115 User curve #:Reset
•
instantaneous
•
disk emulation
disk emulation
_:101 User curve #:Time dial 0.05 to 15.00 1.00
Dyn.s: AR off/n.rdy
_:28 User curve #:Effect. by
AR off/n.ready
•
no
•
yes
no
_:35 User curve #:Stage
blocked
•
no
•
yes
no
Dyn.set: AR cycle 1
_:29 User curve #:Effected by
AR cycle 1
•
no
•
yes
no
_:36 User curve #:Stage
blocked
•
no
•
yes
no
_:14 User curve #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:102 User curve #:Time dial 0.05 to 15.00 1.00
Dyn.set: AR cycle 2
_:30 User curve #:Effected by
AR cycle 2
•
no
•
yes
no
_:37 User curve #:Stage
blocked
•
no
•
yes
no
_:15 User curve #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:103 User curve #:Time dial 0.05 to 15.00 1.00
Dyn.set: AR cycle 3
_:31 User curve #:Effected by
AR cycle 3
•
no
•
yes
no
_:38 User curve #:Stage
blocked
•
no
•
yes
no
Protection and Automation Functions
6.6 Directional Overcurrent Protection, Phases
SIPROTEC 5, Overcurrent Protection, Manual 431
C53000-G5040-C017-8, Edition 07.2017