Addr. Parameter C Setting Options Default Setting
_:4861:15 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:4861:21 Definite-T 1:Operate
delay
0.00 s to 60.00 s 0.30 s
Dyn.set: AR cycle 3
_:4861:31 Definite-T 1:Effected by
AR cycle 3
•
no
•
yes
no
_:4861:38 Definite-T 1:Stage
blocked
•
no
•
yes
no
_:4861:16 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:4861:22 Definite-T 1:Operate
delay
0.00 s to 60.00 s 0.30 s
Dyn.s: AR cycle>3
_:4861:32 Definite-T 1:Effected by
AR cycle gr. 3
•
no
•
yes
no
_:4861:39 Definite-T 1:Stage
blocked
•
no
•
yes
no
_:4861:17 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:4861:23 Definite-T 1:Operate
delay
0.00 s to 60.00 s 0.30 s
Dyn.s: Cold load PU
_:4861:33 Definite-T 1:Effect. b.
cold-load pickup
•
no
•
yes
no
_:4861:40 Definite-T 1:Stage
blocked
•
no
•
yes
no
_:4861:18 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:4861:24 Definite-T 1:Operate
delay
0.00 s to 60.00 s 0.30 s
Protection and Automation Functions
6.7 Directional Overcurrent Protection, Ground
SIPROTEC 5, Overcurrent Protection, Manual 457
C53000-G5040-C017-8, Edition 07.2017