Figure 6-119
Structure/Embedding of the Directional Function in Protection Function Groups
Non-Directional Sensitive Ground-Fault Detection
The Non-directional sensitive ground-fault detection function can be used in protection function groups
that only make the zero-sequence system (3I0) available. The function comes factory-set with a non-direc-
tional 3I0> stage.
The following stages can be operated simultaneously within the function:
4 non-directional 3I0> stages
2 non-directional Y0> stages
2 non-directional pulse-pattern detection stages
The general functionality works across stages on the function level.
The group-indications output logic generates the following group indications of the entire function by the
logical OR from the stage-selective indications:
Pickup
Operate indication
Protection and Automation Functions
6.15 Sensitive Ground-Fault Detection
SIPROTEC 5, Overcurrent Protection, Manual 563
C53000-G5040-C017-8, Edition 07.2017