EasyManua.ls Logo

Siemens 7SJ85 - Page 620

Siemens 7SJ85
1638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
The following figure shows a simplified network that applies the pulse-pattern detection method.
The pulse pattern in the ground current 3I0 is generated by switching on and off a capacitor in parallel to the
arc-suppression coil:
When the capacitor is switched on, an additional capacitive ground current is generated and the 3I0
compensation changes.
When the capacitor is switched off, the additional capacitive ground current is vanished and the 3I0
compensation returns to the normal state.
[dw_pulse detection network, 1, en_US]
Figure 6-146
Network that Uses the Pulse-Pattern Detection
Cs Capacitance of the switched capacitor
L Inductance of the arc-suppression coil
Pulse Pattern during a Ground Fault
The following figure shows the 3I0 pulse pattern in an overcompensated system for a low-impedance ground
fault and a high-impedance ground fault.
For low-impedance ground faults, the 3I0 pulse pattern exists only in the faulty feeder.
For high-impedance ground faults, the pulse pattern is also present in the healthy feeders with lower
amplitude but in phase opposition to the faulty feeder.
Applying a different switch-on/switch-off duration allows distinguishing between faulty and healthy
feeders in case of high-impedance ground faults.
Protection and Automation Functions
6.15 Sensitive Ground-Fault Detection
620 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017

Table of Contents

Related product manuals