EasyManua.ls Logo

Siemens 7SJ85 - Page 668

Siemens 7SJ85
1638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Thermal Replica
The protection function calculates the overtemperature from the phase currents on the basis of a thermal
single-body model according to the thermal differential equation with
[fo_TOLP_diffgl, 1, en_US]
With the following standardization:
[fo_TOLP_normie, 1, en_US]
Θ Current overtemperature, in relation to the final temperature at a maximum permis-
sible phase current k I
rated, obj
Δ ϑ
rated obj
Overtemperature of the protected object set at rated current
τ
th
Thermal time constant (temperature rise/cooling) of the protected object. The value is
calculated internally.
K This factor indicates the maximum continuous permissible phase current. The factor
refers to the rated current of the protected object (K = I
max
/I
rated, obj
) and is calculated
internally.
I
rated, obj
Rated current of the protected object
[dw_TOLP_Temperature, 1, en_US]
Figure 6-170 Temperature History for Different Overload Currents ( K-factor = 1.1)
The overtemperature is calculated separately for each phase. The current overtemperature can be obtained
from the operational measured values. It is shown in percent. An indication of 100 % means that the thermal
threshold has been reached. The maximum overtemperature of the phases is regarded as the tripping temper-
ature. This means that the highest of the 3 phase currents is always assumed.
Protection and Automation Functions
6.20 Thermal Overload Protection, User-Defined Characteristic Curve
668 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017

Table of Contents

Related product manuals