[dw_load shedding_Power crit.<0, 1, en_US]
Figure 6-215 Power-Criterion Checking at Phi (power criterion) ≤ 0
[dw_load shedding_Power crit.>0, 1, en_US]
Figure 6-216 Power-Criterion Checking at Phi (power criterion) > 0
The power criterion contains the check of the current criterion and of the power-angle criterion.
You can determine whether to check the power criterion or not by setting the Power criterion parameter.
The power criterion is carried out only when the Power criterion parameter is set to yes.
The working method of the current criterion and of the power-angle criterion differ at Phi (power crite-
rion) ≤ 0 and Phi (power criterion) > 0.
Protection and Automation Functions
6.34 Underfrequency Load Shedding
776 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017