EasyManua.ls Logo

Siemens FS20 - Network Module (SAFEDLINK)

Siemens FS20
188 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Updating the firmware
Station: Updating the FW of
the main CPU and additional CPUs
29
131 |
188
Building Technologies
009052_s_en_
--
Fire Safety
2016
-
-
02
5. Confirm the firmware update with 'Yes' or reject the firmware update with 'No'.
The following window is opened:
6. Click on 'OK'.
The following window is opened:
7. Select 'Run in background' in order to run the firmware update in the
background while continuing to work in SintesoWorks.
The active firmware update is indicated by the symbol on the right-
hand side of the status bar.
The progress of the firmware update is displayed on the 'Progress' tab.
Open the 'Progress' tab in the 'View' > 'Progress' menu.
Pop-up windows in the bottom right-hand corner of the software will notify
you when the firmware download and the firmware update are complete.
After the restart, the 'Station' display shows the available BDVs. It is not
necessary to install a BDV at this point.

Table of Contents

Other manuals for Siemens FS20

Related product manuals