EasyManua.ls Logo

ABB REG670 - Page 270

ABB REG670
1298 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
degrees. It can be observed in Figure 112 that the angle reaches 180 degrees when the
complex impedance Z(R, X) crosses the impedance line SE RE. It then changes the
sign, and continues from -180 degrees to 0 degrees, and so on. Figure 112 shows the
rotor (power) angle and the magnitude of Z(R, X) against time for the case from Figure
111.
0 200 400 600 800 1000 1200 1400
-4
-3
-2
-1
0
1
2
3
4
Time in millis econds
®
Impedance Z in Ohm and rotor angle in radian
®
|Z| in Ohms
angle in rad
normal
load
fault 500 ms
Z(R,X) cros s e d
the im pe da nce line , Z-line,
conne cting points SE - RE
fault
occurrs
Z(R, X) under fault lies
on the impedance line
or near (for 3-ph faults )
Unde r 3-pha s e fault
condition rotor a ngle
of a pp. ±180 de gree s
is m ea s ure d ...
rotor (power)
angle
|Z|
IEC10000110-2-en.vsd
1
2
3
1
0
IEC10000110 V2 EN
Figure 112: Rotor (power) angle and magnitude of the complex impedance Z(R,
X) against the time
In order to be able to fully understand the principles of OOSPPAM, a stable case, that
is, a case where the disturbance does not make a generator to go out-of-step, must be
shown.
Section 7 1MRK502052-UEN B
Impedance protection
264
Technical manual

Table of Contents

Other manuals for ABB REG670

Related product manuals