Set value for the
parameter
CurrentInput
Set value for the
parameter
VoltageInput
Comment
Phase1 Phase2-Phase3 Directional overcurrent function for the first phase is
obtained. Typical setting for
RCADir
is +30° or +45°
Phase2 Phase3-Phase1 Directional overcurrent function for the second phase
is obtained. Typical setting for
RCADir
is +30° or +45°
Phase3 Phase1-Phase2 Directional overcurrent function for the third phase is
obtained. Typical setting for
RCADir
is +30° or +45°
Unbalance current or voltage measurement shall not be used when the directional
feature is enabled.
Two types of directional measurement principles are available, I & U and IcosPhi&U.
The first principle, referred to as "I & U" in the parameter setting tool, checks that:
the magnitude of the measured current is bigger than the set pick-up level
the phasor of the measured current is within the operating region (defined by the
relay operate angle, ROADir parameter setting; see figure
272).
U=-3U0
Ipickup
Operate region
I=3Io
mta line
RCADir
ROADir
en05000252.vsd
IEC05000252 V1 EN
Figure 272: I & U directional operating principle for CVGAPC function
where:
RCADir
is -75°
ROADir
is 50°
The second principle, referred to as "IcosPhi&U" in the parameter setting tool, checks
that:
that the product I·cos(Φ) is bigger than the set pick-up level, where Φ is angle
between the current phasor and the mta line
that the phasor of the measured current is within the operating region (defined by
the I·cos(Φ) straight line and the relay operate angle, ROADir parameter setting;
see figure 272).
Section 11 1MRK502052-UEN B
Multipurpose protection
580
Technical manual