Cause
number
Name Description Supported
-32 persistantIntermedi
ateState
Switch stopped in intermediate state X
-33 switchReturnedToIn
itPos
Switch returned to the initial position X
-34 switchInBadState Switch is in a bad position state X
-35 notExpectedFinalPo
sition
Switch did not reach the expected final position X
Table 398: Translation of cause values for IEC61850 edition 2 and edition 1
Internal Cause
Number
AddCause in IEC61850-8-1 Name
Ed 2 Ed 1
0 25 0 None
1 1 1 Not-supported
2 2 2 Blocked-by-switching-hierarchy
3 3 3 Select-failed
4 4 4 Invalid-position
5 5 5 Position-reached
6 6 6 Parameter-change-in-execution
7 7 7 Step-limit
8 8 8 Blocked-by-Mode
9 9 9 Blocked-by-process
10 10 10 Blocked-by-interlocking
11 11 11 Blocked-by-synchrocheck
12 12 12 Command-already-in-execution
13 13 13 Blocked-by-health
14 14 14 1-of-n-control
15 15 1 Abortion-by-cancel
16 16 16 Time-limit-over
17 17 17 Abortion-by-trip
18 18 18 Object-not-selected
19 19 3 Object-already-selected
20 20 3 No-access-authority
21 21 - Ended-with-overshoot
22 22 - Abortion-due-to-deviation
23 23 - Abortion-by-communication-loss
24 24 -23 Blocked-by-command
26 26 6 Inconsistent-parameters
27 27 12 Locked-by-other-client
-22 0 -22 Wrong_CTL_Model
Table continues on next page
Section 14 1MRK502052-UEN B
Control
708
Technical manual