Internal Cause
Number
AddCause in IEC61850-8-1 Name
Ed 2 Ed 1
-24 24 -24 Blocked_for_Open_Cmd
-25 24 -25 Blocked_For_Close_Cmd
-30 24 -30 longOperationTime
-31 16 -31 switchNotStartMoving
-32 16 -32 persistantIntermediateState
-33 22 -33 switchReturnedToInitPos
-34 4 -34 switchInBadState
-35 22 -35 notExpectedFinalPosition
14.3.4 Bay control QCBAY
14.3.4.1 Functionality
The Bay control QCBAY function is used together with Local remote and local
remote control functions to handle the selection of the operator place per bay. QCBAY
also provides blocking functions that can be distributed to different apparatuses within
the bay.
14.3.4.2 Function block
LR_OFF PSTO
LR_LOC UPD_BLKD
LR_REM CMD_BLKD
LR_VALID LOC
BL_UPD STA
BL_CMD
QCBAY
REM
IEC10000048-2-en.vsd
IEC10000048 V2 EN
Figure 330: QCBAY function block
14.3.4.3 Signals
Table 399: QCBAY Input signals
Name
Type Default Description
LR_OFF BOOLEAN 0 External Local/Remote switch is in Off position
LR_LOC BOOLEAN 0 External Local/Remote switch is in Local position
LR_REM BOOLEAN 0 External Local/Remote switch is in Remote
position
LR_VALID BOOLEAN 0 Data representing the L/R switch position is valid
BL_UPD BOOLEAN 0 Steady signal to block the position updates
BL_CMD BOOLEAN 0 Steady signal to block the command