Name Values (Range) Unit Step Default Description
MasterAddres 0 - 65519 - 1 1 Master address
Obj1DefVar 1:BISingleBit
2:BIWithStatus
- - 1:BISingleBit Object 1, default variation
Obj2DefVar 1:BIChWithoutTim
e
2:BIChWithTime
3:BIChWithRelTim
e
-
- 3:BIChWithRelTim
e
Object 2, default variation
Obj3DefVar 1:DIWithoutFlag
2:DIWithFlag
- - 1:DIWithoutFlag Object 3, default variation
Obj4DefVar 1:DIChWithoutTim
e
2:DIChWithTime
3:DIChWithRelTim
e
-
- 3:DIChWithRelTim
e
Object 4, default variation
Obj10DefVar 1:BO
2:BOStatus
- - 2:BOStatus Object 10, default variation
Obj20DefVar 1:BinCnt32
2:BinCnt16
5:BinCnt32WoutF
6:BinCnt16WoutF
-
- 5:BinCnt32WoutF Object 20, default variation
Obj22DefVar 1:BinCnt32EvWout
T
2:BinCnt16EvWout
T
5:BinCnt32EvWith
T
6:BinCnt16EvWith
T
- - 1:BinCnt32EvWou
tT
Object 22, default variation
Obj30DefVar 1:AI32Int
2:AI16Int
3:AI32IntWithoutF
4:AI16IntWithoutF
5:AI32FltWithF
6:AI64FltWithF
-
- 3:AI32IntWithoutF Object 30, default variation
Obj32DefVar 1:AI32IntEvWoutF
2:AI16IntEvWoutF
3:AI32IntEvWithFT
4:AI16IntEvWithFT
5:AI32FltEvWithF
6:AI64FltEvWithF
7:AI32FltEvWithFT
8:AI64FltEvWithFT
- - 1:AI32IntEvWoutF Object 32, default variation
Table 475: MSTSER Non group settings (advanced)
Name
Values (Range) Unit Step Default Description
ValMasterAddr No
Yes
- - Yes Validate source (master) address
AddrQueryEnbl No
Yes
- - Yes Address query enable
tApplConfTout 0.00 - 300.00 s 0.01 10.00 Application layer confim timeout
ApplMultFrgRes No
Yes
- - Yes Enable application for multiple fragment
response
Table continues on next page
1MRK502052-UEN B Section 14
Control
777
Technical manual

Table of Contents

Other manuals for ABB REG670