Name Values (Range) Unit Step Default Description
tUREvBufTout2 0.00 - 60.00 s 0.01 5.00 Unsolicited response class 2 event buffer
timeout
UREvCntThold3 1 - 100 - 1 5 Unsolicited response class 3 event count
report treshold
tUREvBufTout3 0.00 - 60.00 s 0.01 5.00 Unsolicited response class 3 event buffer
timeout
DelOldBufFull No
Yes
- - No Delete oldest event when buffer is full
ExtTimeFormat LocalTime
UTC
- - UTC External time format
DNPToSetTime No
Yes
- - No Allow DNP to set time in IED
tSynchTimeout 30 - 3600 s 1 1800 Time synch timeout before error status is
generated
TSyncReqAfTout No
Yes
- - No Time synchronization request after
timeout
Averag3TimeReq No
Yes
- - No Use average of 3 time requests
PairedPoint No
Yes
- - Yes Enable paired point
tSelectTimeout 1.0 - 60.0 s 0.1 30.0 Select timeout
tBrokenConTout 0 - 3600 s 1 0 Broken connection timeout
tKeepAliveT 0 - 3600 s 1 10 Keep-Alive timer
Table 480: MST3TCP Non group settings (basic)
Name
Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation Off / On
SlaveAddress 0 - 65519 - 1 1 Slave address
MasterAddres 0 - 65519 - 1 1 Master address
ValMasterAddr No
Yes
- - Yes Validate source (master) address
MasterIP-Addr 0 - 18 IP
Address
1 0.0.0.0 Master IP-address
MasterIPNetMsk 0 - 18 IP
Address
1 255.255.255.255 Master IP net mask
Obj1DefVar 1:BISingleBit
2:BIWithStatus
- - 1:BISingleBit Object 1, default variation
Obj2DefVar 1:BIChWithoutTim
e
2:BIChWithTime
3:BIChWithRelTim
e
-
- 3:BIChWithRelTim
e
Object 2, default variation
Obj3DefVar 1:DIWithoutFlag
2:DIWithFlag
- - 1:DIWithoutFlag Object 3, default variation
Table continues on next page
1MRK502052-UEN B Section 14
Control
783
Technical manual

Table of Contents