Name Values (Range) Unit Step Default Description
Obj4DefVar 1:DIChWithoutTim
e
2:DIChWithTime
3:DIChWithRelTim
e
-
- 3:DIChWithRelTim
e
Object 4, default variation
Obj10DefVar 1:BO
2:BOStatus
- - 2:BOStatus Object 10, default variation
Obj20DefVar 1:BinCnt32
2:BinCnt16
5:BinCnt32WoutF
6:BinCnt16WoutF
-
- 5:BinCnt32WoutF Object 20, default variation
Obj22DefVar 1:BinCnt32EvWout
T
2:BinCnt16EvWout
T
5:BinCnt32EvWith
T
6:BinCnt16EvWith
T
- - 1:BinCnt32EvWou
tT
Object 22, default variation
Obj30DefVar 1:AI32Int
2:AI16Int
3:AI32IntWithoutF
4:AI16IntWithoutF
5:AI32FltWithF
6:AI64FltWithF
-
- 3:AI32IntWithoutF Object 30, default variation
Obj32DefVar 1:AI32IntEvWoutF
2:AI16IntEvWoutF
3:AI32IntEvWithFT
4:AI16IntEvWithFT
5:AI32FltEvWithF
6:AI64FltEvWithF
7:AI32FltEvWithFT
8:AI64FltEvWithFT
- - 1:AI32IntEvWoutF Object 32, default variation
Table 481: MST3TCP Non group settings (advanced)
Name
Values (Range) Unit Step Default Description
AddrQueryEnbl No
Yes
- - Yes Address query enable
tApplConfTout 0.00 - 300.00 s 0.01 10.00 Application layer confim timeout
ApplMultFrgRes No
Yes
- - Yes Enable application for multiple fragment
response
ConfMultFrag No
Yes
- - Yes Confirm each multiple fragment
UREnable No
Yes
- - Yes Unsolicited response enabled
UREvClassMask Off
Class 1
Class 2
Class 1 and 2
Class 3
Class 1 and 3
Class 2 and 3
Class 1, 2 and 3
- - Off Unsolicited response, event class mask
Table continues on next page