en05000161.vsd
Disturbance report
Record no. N
Record no. N+1 Record no. N+100
General dist.
information
Indications
Trip
values
Event
recordings
Disturbance
recording
Event list
IEC05000161 V1 EN
Figure 443: Disturbance report structure
Up to 100 disturbance reports can be stored. If a new disturbance is to be recorded
when the memory is full, the oldest disturbance report is overwritten by the new one.
The total recording capacity for the disturbance recorder is depending of sampling
frequency, number of analog and binary channels and recording time. Figure
444
shows the number of recordings versus the total recording time tested for a typical
configuration, that is, in a 50 Hz system it is possible to record 100 where the average
recording time is 3.4 seconds. The memory limit does not affect the rest of the
disturbance report (Event list (EL), Event recorder (ER), Indications (IND) and Trip
value recorder (TVR)).
100
400 s
350300
40
60
80
40 analog
96 binary
20 analog
96 binary
3,4 s
6,3 s
6,3 s
60 Hz
50 Hz
6,3 s
3,4 s
250
Total recording time
Number of recordings
en05000488.vsd
IEC05000488 V1 EN
Figure 444: Example of number of recordings versus the total recording time
Section 16 1MRK502052-UEN B
Monitoring
966
Technical manual