EasyManua.ls Logo

AIXTRON CRIUS II - Run and Vent Lines

Default Icon
194 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
crius_II_en_00, Edition 06/2010
72 CONFIDENTIAL AIXTRON - Dokumentation
Description System Manual
Gas system CRIUS II
3
3.6.2 Run and vent lines
The CRIUS II is equipped with three run lines. They are used to lead the pro-
cess gas from the sources to the reactor chamber. Digital flow controllers con-
trol the process gas flow:
Run lines
Hydride run line
Leads from the hydride sources to the lower plenum of the showerhead.
See Fig. 3-20, 71, item F.
MO1 run line
Leads from the MO1 sources to the upper plenum of the showerhead.
See Fig. 3-20, 71, item J.
MO2 run line
Leads from the MO2 sources to the upper plenum of the showerhead.
See Fig. 3-20, 71, item H.
Vent lines
For each run line, there is also a vent line. They lead past the reactor chamber
into the vacuum system. See Fig. 3-20, 71, item K.
Switching between run and vent lines
A 5/2-way valve is used to switch between a run and a vent line. The following
two states are possible:
To avoid pressure compensation reactions during the switching processes
between run and vent lines, the pressure in the run/vent lines and in the reac-
tor chamber will be held at the same level.
Open: The process gas flows through the run
line into the reactor. No process gas
flows in the vent line.
Closed: The process gas flows through the
vent line and passes the reactor. Only
carrier gas flows in the run line. H
2
is
normally used for this.

Table of Contents