Mains voltage
Mains voltage supply data
Description Symbol Unit
KMV03.1R-
A05K0-P-D7-
ET-NNNN
KMV03.1R-
B0007-P-D7-
ET-NNNN
KMV03.1R-
I01K5-P-D7-
ET-NNNN
KMV03.1R-
W06K0-P-D7-
ET-NNNN
Mains frequency
f
LN
Hz 50...60
Tolerance input frequency Hz ±2
Maximum allowed mains
frequency change
Δf
LN
/Δt
Hz/s 1
Rotary field condition None
Short circuit current rating SCCR A rms 42000
Nominal mains voltage
U
LN_nenn
V 3 AC 400
Three-phase mains voltage at TN-
S, TN-C, TT mains
U
LN
V AC 380…500
Mains voltage, three-phase at IT
mains
1)
U
LN
V AC 380…500
Mains voltage, three-phase at
Corner-grounded-Delta mains
2)
U
LN
V Not allowed
Tolerance rated input voltage U
LN
% ±10
Minimum inductance of mains
supply (mains phase inductance)
3)
L
min
µH 50
Assigned mains filter with
integrated mains choke
KNK03.1A-
NR-A0008-P-
U226-A4-
NNNN
KNK03.1A-
NR-B0012-P-
U226-A4-
NNNN
KNK03.1A-
NR-I0002-P-
U226-A4-
NNNN
KNK03.1A-
NR-W0010-P-
U226-A4-
NNNN
Minimum short circuit power of the
mains for failure-free operation
S
k_min
MVA 1.5
Inrush current
I
L_trans_max
_on
A 8.1 … 13
Maximum allowed ON-OFF cycles
per minute
4)
1
Power factor TPF
L
) at P
DC_cont
with mains choke; U
LN_nenn
TPF 0.99
Power factor of fundam.
component DPF at P
DC_cont
with
mains choke
cosφ
h1
0.99
Mains connection power at
P
DC_cont
; U
LN_nenn
with mains choke
S
LN
kVA 5.7 8.4 1.6 6.6
Rated input current
I
LN
A 8.1 12.0 2.3 9.5