Use the F6000 Control Panel to carry out the reach test. The test applies
an AB fault to a distance relay:
• Set up the source table to use VA and VB as the active sources.
• Use the Inputs tab of the Settings display to define the sense
condition.
• Select the settings needed for the test in the Ramp/Set sources
section.
• Activate VA and VB, and decrease the voltage until the relay
responds.
Source Table
To begin the test, type the required settings into the source table of the
Control Panel:
1. Click Tools|F6000 Control Panel in the top menu bar.
The F6000 Control Panel appears (Figure 5.2 on page 5-3).
2. Type these settings into the Amplitude column of the source table
(I1 and I2 keep their default settings):
VA = 30
VB = 30
VC = 67
I3 = 0
3. Type these settings into the Phase column of the source table (VA, VB,
and VC keep their default settings):
I1 = 315
I2 = 135
I3 = 0
The source table should appear as it does in Figure 5.19
on page 5-23.