Use the F6000 Control Panel to carry out the reach test. The test applies
an AB fault to a distance relay:
Set up the source table to use VA and VB as the active sources.
Use the Inputs tab of the Settings display to define the sense
condition.
Select the settings needed for the test in the Ramp/Set sources
section.
Activate VA and VB, and decrease the voltage until the relay
responds.
Source Table
To begin the test, type the required settings into the source table of the
Control Panel:
1. Click Tools|F6000 Control Panel in the top menu bar.
The F6000 Control Panel appears (Figure 5.2 on page 5-3).
2. Type these settings into the Amplitude column of the source table
(I1 and I2 keep their default settings):
VA = 30
VB = 30
VC = 67
I3 = 0
3. Type these settings into the Phase column of the source table (VA, VB,
and VC keep their default settings):
I1 = 315
I2 = 135
I3 = 0
The source table should appear as it does in Figure 5.19
on page 5-23.