F6000 Family of Power System Simulators User Guide
72A-1589 Rev. C 02/01 5-27
D
DD
D
R
RR
R
A
AA
A
F
FF
F
T
TT
T
3
33
3
/
//
/
5
55
5
/
//
/0
00
0
1
11
1
15. Click System Output at the bottom of the Control Panel.
The indicator lights for outputs 1 through 6 in the lower right-hand
corner of the Control panel are green.
16. Click and hold the Ramp/Set down arrow in the Ramp/Set sources
section until the relay responds.
In the source table, observe VA and VB ramp down in 0.1 V
increments until the relay picks up. At that point, the values for VA
and VB freeze, and the red indicator light for input 1 turns on.
17. Click System Output again to turn the sources off.