Solution 862
Installation Manual
Swinger Shutdown Count For Dialler
LOCATION 324
6
Location Description
324
Swinger Shutdown Count For Dialler (0-15)
Table 79: Swinger Shutdown Count For Dialler Location
This location determines the number of times the dialler can be triggered before any lockout
options will take effect. A minimum of one zone must be programmed for lockout dialler for
this location to be effective. Refer to Zone Options 1 on page 167 to program zones for
lockout dialler.
Only alarms triggered from zone inputs will increment the swinger shutdown counter. This
means alarms such as codepad panic, code retries and any other system alarms will not effect
the swinger shutdown count.
While the sirens are operating, the counter for the dialler is only incremented by the first zone
that causes the alarm. Any other zones that are triggered during siren time will not effect the
counter. While the dialler is on line, its counter is only incremented by the first zone that
causes the alarm. Any other zones that are triggered while the dialler is on line will not effect
the counter.
When the swinger shutdown count (As programmed in "LOCATION 324") has been reached,
all zones that have been triggered will be locked out according to their individual lockout
settings.
If "Lockout Dialler" has been enabled for any zone, the last restore signal will not be
transmitted until the system has been disarmed.
Example
All eight zones have been programmed for lockout dialler with a swinger shutdown count of 6.
If zone 1 triggers an alarm, the swinger shutdown count will decrement by one at the time the
control panel makes the call to a swinger shutdown count of 5.
If zone 1 re-triggers the dialler, the swinger shutdown count will be decremented by one to a
swinger shutdown count of 4. If zone 1 re-triggers the dialler 3 more times, the swinger
shutdown count will be 1.
If zone 2 triggers an alarm, the swinger shutdown count will be decremented by one to a
swinger shutdown count of zero, therefore, locking out zone 2 from activating the dialler again
until the system has been reset. However, at this point in time, the swinger shutdown count for
the dialler has again a lockout count of 6 and the process of swinger shutdown for the
remaining zones including zone 1 begin again until all zones have been locked out.