System Reporting Information 177
Zone Status Trouble Reports
LOCATION 327 – 328
23
Location Description
327
Zone Trouble Report
328
Zone Trouble Restore Report
Table 81: Zone Status - Trouble Report Locations
A zone is in trouble when it is unsealed at the end of exit time. A "Sensor Trouble" report
(Contact ID Event Code 380) will be transmitted to indicate that one or more zones have been
automatically isolated by the system. 24-hour zones that are unsealed at the end of exit time
will not transmit a "Sensor Trouble" report as the restore for that zone is still outstanding.
A "Sensor Trouble" restore report will be transmitted for burglary zones when the zone reseals
or when the system is next disarmed (which ever happens first). A 24-hour zone will only
transmit a restore signal when it has resealed.
The trouble code parameter is used as the expansion digit in 4+2 Format. It has no effect on
Contact ID Format as a "Sensor Trouble" report will always be reported on event code 380.
If "Sensor Trouble" reports are not required, program "LOCATION 327 – 328" with a zero.