Outputs
The
Solution 862
control panel has four fully programmable outputs on the main PCB and
one other programmable output that operates the codepad buzzer. These four outputs are
factory default to operate as horn speaker, fire alarm verification, strobe and an internal
screamer.
Outputs 1 – 4 will NOT operate whilst the control panel detects a low battery.
Programmable outputs require four parameters to be programmed in order to operate correctly.
Event Type:
When To Operate
Polarity:
How To Operate
Time Base:
How Long To Operate For
Time Multiplier:
How Often To Operate
Event Polarity Time Time
Type Base Multiplier
When To Operate
Is selected from the output event types listed on page 192.
Each digit should be entered into the two corresponding
locations for the output event type required.
How To Operate
Is selected from "Table 101: Event Type Polarities” on page
199. This determines whether the output remains operating for
the duration of the event, pulses for the duration, operates once
only (one shot) or latches on.
How Long To Operate For
Is determined by a time base and a multiplier. Refer to
"Timing Of Outputs" on page 201 for further information.
How Often To Operate For
Is determined by a time base and a multiplier. Refer to
"Timing Of Outputs" on page 201 for further information.
Output Defaults
Location 368 - 373 Location 374 - 379 Location 380 - 385
Output 1
1 14 0 0 0 0
Output 2
2 7 10 2 1 5
Strobe
2 0 6 4 0
Default For Horn Default For Default For Strobe
Speaker Fire Alarm Verification (Reset In 8 Hrs)
Location 386 – 391 Location 392 – 397
Relay
1 15 1 0 0 0
Codepad
0 13 2 1 0 1
Default For Default For Entry/Exit
Sirens Running Warning + Day Alarm
Event Type Polarity Time Base Time Multiplier
ISSUE130 Electronics Design and Manufacturing Pty Limited
8