Parameter 07.001 Analog Input 1
Short description Displays the value of analog input 1
Mode Openloop
Minimum -100.00 Maximum 100.00
Default Units %
Type 16 Bit Volatile Update Rate 4ms
Display Format Standard Decimal Places 2
Coding RO, FI, ND, NC, PT
The Analog input 1 can operate in different modes as defined by AnalogInput1Mode (07.007) including current modes. See AnalogI/O.
Voltage mode: Resolution of 11 bits. It is a single ended unipolar voltage input 0V-10V
Current mode: Resolution of 11 bits. It is a single ended unipolar 0-20mA
Unidrive M200 Parameter Reference Guide