If CoolingFancontrol (06.045) = 5 is the same as CoolingFancontrol (06.045) = 2 but with an additional lower temperature threshold that causes the fan to run at low speed if
StackTemperature (07.004) is above the lower threshold - “theatre mode”. In some applications this may prevent the fan running at full speed and so keep the audible noise down to a
minimum. This mode is not available on size 1 and so if selected, mode 2 is used instead.
Parameter 06.047 Input Phase Loss Detection Mode
Short description Defines how the input phase loss is detected
Mode Openloop
Minimum 0 Maximum 2
Default 0 Units
Type 8 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 0
Coding RW, TE
Value Text
0 Full
1 RIPPLE
2 diS
Input phase loss is detected by monitoring the d.c. link voltage ripple which increases with load. When compared to normal operation, if an input phase is missing or there is excessive input
phase imbalance the d.c. link ripple level is higher. The high ripple level is detected to initiate a PH.Lo trip. For drive sizes 8 and above an additional input phase loss detection is provided by
direct monitoring of the supply voltages (PH.Lo trip). Unlike the d.c. voltage ripple based detection which can only operate when the drive is enabled and on load, the additional input phase loss
detection can operate whether the drive is enabled or not. InputPhaseLossDetectionMode (06.047) defines the methods used for input phase loss detection provided by the drive.
Input Phase Loss Detection Mode (06.047) Drive Active (10.002) = 0 Drive Active (10.002) = 1
0 *Direct input phase loss detection
*Direct input phase loss detection
D.c. link voltage ripple detection
1 *Direct input phase loss detection D.c. link voltage ripple detection
2 No input phase loss detection No input phase loss detection
*Frame sizes 8 and above
Input phase loss detection can be disabled when the drive is required to operate from a d.c. supply connected to the d.c. link or from a single phase supply. If the drive operates from a single
phase supply or a supply with high levels of phase imbalanced under load the input stage and d.c. link thermal protection system may produce a OHtdcbus trip.
Parameter 06.048 Supply Loss Detection Level
Short description Defines the threshold for indicating when the supply loss condition is detected
Mode Openloop
Minimum 0 Maximum VM_SUPPLY_LOSS_LEVEL
Default See exceptions below Units V
Type 16 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 0
Coding RW, VM, RA
Voltage Default Value
110V 205
200V 205
400V 410
575V 540
690V 540
Defines the threshold for indicating when the supply loss condition is detected.
The threshold can be adjusted to higher levels using this parameter. If the value is reduced below the default value the default value is used by the drive. If the level is set too high so that supply
loss detection becomes active under normal operating conditions, the motor will coast to a stop.
Parameter 06.051 Hold Supply Loss Active
Short description Hold Supply Loss Active
Mode Openloop
Minimum 0 Maximum 1
Default 0 Units
Type 1 Bit Volatile Update Rate 1ms read
Display Format Standard Decimal Places 0
Coding RW, NC
If supply loss is detected (i.e. SupplyLoss (10.015) = 1) or HoldSupplyLossActive (06.051) = 1 the supply loss indication and the action taken on supply loss will be active. For
example, HoldSupplyLossActive (06.051) can be controlled by an external rectifier or a Regen system (via a digital input) to prevent power from being taken from the supply if supply loss ride-
through mode is being used until the input system is ready to provide power. This can allow for the charge system in an external rectifier to complete the charging, or it can allow a Regen
system to become synchronised.
Parameter 06.052 Motor Pre-heat Current Magnitude
Short description Defines the current in the motor when the state machine is in the stop state
Mode Openloop
Minimum 0 Maximum 100
Default 0 Units %
Type 8 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 0
Coding RW
See HoldZeroFrequency (06.008).
Parameter 06.058 Output Phase Loss Detection Time
Short description Output Phase Loss Detection Time
Mode Openloop
Minimum 0 Maximum 3
Default 0 Units
Type 8 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 0
Coding RW, TE
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10
95