Voltage Default Value
110V 390
200V 390
400V 780
575V 930
690V 1120
BrakingIGBTLowerThreshold (06.073) defines the lowest level of D.c.LinkVoltage (05.005) where the braking IGBT will become active and BrakingIGBTUpperThreshold (06.074) defines
the level of D.c.LinkVoltage (05.005) where the braking IGBT will be on continuously. When the braking IGBT is turned on it will remain on for at least 1ms. The braking IGBT on-time is defined
by the thresholds and the d.c. link voltage as given in the table below where L = BrakingIGBTLowerThreshold (06.073) and U = BrakingIGBTUpperThreshold (06.074).
D.c. link voltage level On-time
D.c.LinkVoltage (05.005) < L 0%
L ≤ D.c.LinkVoltage (05.005) ≤ U [(D.c.LinkVoltage (05.005) - L) / (U - L)] x 100%
D.c.LinkVoltage (05.005) ≥ U 100%
As the D.c.LinkVoltage (05.005) rises above the lower threshold the braking IGBT is active with an on/off ratio of 1/100. As the voltage rises further, the on/off ratio increases until at the upper
threshold the braking IGBT is on continuously. The upper and lower voltage threshold can be set up so that braking resistors in drives with parallel connected d.c. links will share the braking
load.
If BrakingIGBTLowerThreshold (06.073)BrakingIGBTUpperThreshold (06.074) then the braking IGBT is off when D.c.LinkVoltage (05.005) BrakingIGBTUpperThreshold (06.074) and
on if D.c.LinkVoltage (05.005)BrakingIGBTUpperThreshold (06.074). This method of control is the same as that used in Commander SK and the default values for the braking thresholds
are equal to the braking thresholds in Commander SK.
Unless sharing between braking resistors is required the braking thresholds do not normally need to be adjusted. Care should be taken when reducing the thresholds because if either threshold
is below the maximum value of the peak rectified supply voltage the braking resistor could take power from the supply.
The list below gives conditions that will disable the braking IGBT:
1. BrakingIGBTUpperThreshold (06.074) = 0, or LowVoltageBrakingIGBTThresholdSelect (06.076) = 1 and LowVoltageBrakingIGBTThreshold (06.075) = 0.
2. The drive is in the under-voltage state.
3. A priority 1, 2 or 3 trip is active.
4. There is a fault in the control system power supply.
5. The hardware or software over-temperature systems indicate that the braking resistor is too hot.
6. A braking IGBT over-current trip is active OIBrake.
Parameter 06.074 Braking IGBT Upper Threshold
Short description Defines the level of the d.c. bus voltage where the braking IGBT will be on continuously
Mode Openloop
Minimum −VM_DC_VOLTAGE_SET Maximum VM_DC_VOLTAGE_SET
Default See exceptions below Units V
Type 16 Bit User Save Update Rate Background
Display Format Standard Decimal Places 0
Coding RW, VM, RA
Voltage Default Value
110V 390
200V 390
400V 780
575V 930
690V 1120
See BrakingIGBTLowerThreshold (06.073).
Parameter 06.075 Low Voltage Braking IGBT Threshold
Short description Defines the threshold used for low voltage braking
Mode Openloop
Minimum −VM_DC_VOLTAGE_SET Maximum VM_DC_VOLTAGE_SET
Default 0 Units V
Type 16 Bit User Save Update Rate Background
Display Format Standard Decimal Places 0
Coding RW, VM, RA
If LowVoltageBrakingIGBTThresholdSelect (06.076) = 0 the normal thresholds are used. If LowVoltageBrakingIGBTThresholdSelect (06.076) = 1 then
LowVoltageBrakingIGBTThreshold (06.075) is used for both upper and lower thresholds. This allows a different braking threshold to be set for low voltage operation.
Parameter 06.076 Low Voltage Braking IGBT Threshold Select
Short description Set to 1 enable low voltage IGBT braking
Mode Openloop
Minimum 0 Maximum 1
Default 0 Units
Type 1 Bit Volatile Update Rate Background
Display Format Standard Decimal Places 0
Coding RW
See LowVoltageBrakingIGBTThreshold (06.075)
Parameter 06.077 Low DC Link Operation
Short description Set to 1 to allow a 400V drive to be ran from a 240V supply
Mode Openloop
Minimum 0 Maximum 1
Default 0 Units
Type 1 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 0
Coding RW
On the 400V product setting this bit will enable the drive to run from a 240VAC input. Low DC Link Operation is enabled when LowDCLinkOperation (06.077) is set to one. See figure below.
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10
97