Parameter 02.001 Post Ramp Reference
Short description Displays the output of the ramp system
Mode Open‑loop
Minimum −VM_SPEED_FREQ_REF Maximum VM_SPEED_FREQ_REF
Default Units Hz
Type 32 Bit Volatile Update Rate 16ms
Display Format Standard Decimal Places 2
Coding RO, VM, ND, NC, PT
The PostRampReference (02.001) is combined with HardFrequencyReference (03.022) and the slip compensation frequency to define the output
frequency of the drive. The PostRampReference (02.001) is defined by the output of the ramp system except when the current limits are active (see
Menu 04).
Parameter 02.003 Ramp Hold
Short description Set to 1 to hold the ramp system at its present value
Mode Open‑loop
Minimum 0 Maximum 1
Default 0 Units
Type 1 Bit User Save Update Rate 1ms
Display Format Standard Decimal Places 0
Coding RW
If RampHold (02.003) = 0 the ramp system functions normally. If RampHold (02.003) is set to 1 and SRampEnable (02.006) = 0 the ramp system
output is held at its current level. If RampHold (02.003) is subsequently set to 0 the ramp system output is released and continues to operate normally.
If SRampEnable (02.006) = 1 when RampHold (02.003) is set to 1 the acceleration will ramp towards zero and the frequency will change in an S
curve towards a constant frequency. If a drive stop is requested (i.e. ReferenceOn (01.011) = 0) the ramp hold function is disabled.
Parameter 02.004 Ramp Mode Select
Short description Defines the mode used by the ramp system
Mode Open‑loop
Minimum 0 Maximum 3
Default 1 Units
Type 8 Bit User Save Update Rate 16ms
Display Format Standard Decimal Places 0
Coding RW, TE
Value Text Description
0 Fast Fast ramp
1 Std Standard ramp with normal motor voltage
2 Std.bst Standard ramp with high motor voltage
3 Fst.bst Fast ramp with high motor volts
Acceleration is defined as a positive (forward) or negative (reverse) frequency change away from zero, and deceleration is defined as a change towards