The steady state parameters are converted to equivalent transient model parameters:
R
s
= R
1
L
m
= L
m
L
s
= L
1
+ L
m
L
r
= L
2
+ L
m
σL
s
= L
s
- (L
m
2
/ L
r
)
The equivalent drive parameters are:
StatorResistance (05.017) = R
s
TransientInductance (05.024) = σLs
StatorInductance (05.025) = L
s
Parameter 05.018 Maximum Switching Frequency
Short description Defines the maximum switching frequency that can be used by the drive
Mode Open‑loop
Minimum 0 Maximum VM_MAX_SWITCHING_FREQUENCY
Default 3 Units kHz
Type 8 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 0
Coding RW, TE, VM, RA
Value Text Description
0 0.667 667Hz switching frequency
1 1 1kHz switching frequency
2 2 2kHz switching frequency
3 3 3kHz switching frequency
4 4 4kHz switching frequency
5 6 6kHz switching frequency
6 8 8kHz switching frequency
7 12 12kHz switching frequency
8 16 16kHz switching frequency
MaximumSwitchingFrequency (05.018) should be set to the required PWM switching frequency. The drive inverter will operate at this frequency unless Auto-
switchingFrequencyChangeDisable (05.035) = 0 and the inverter temperature exceeds the threshold for automatic switching frequency reduction (see
InverterTemperature (07.034)). The actual switching frequency is shown in SwitchingFrequency (05.037). The switching frequency has a direct effect on the
sample rate for the current controllers (see CurrentControllerKpGain (04.013)). All other control tasks are at a fixed rate of 1ms.
As default Auto-switchingFrequencyChangeDisable (05.035) = 0 and the system described above is always active. If Auto-
switchingFrequencyChangeDisable (05.035) = 1 then the automatic switching frequency changing system is disabled.
We recommend that a minimum ratio of 12:1 for the switching frequency compared to the maximum output frequency is used.
Parameter 05.019 High Stability Space Vector Modulation
Short description Set to 1 to enable High Stability Space Vector Modulation
Mode Open‑loop
Minimum 0 Maximum 1
Default 0 Units
Type 1 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 0
Coding RW