trips the minimum is 10s. The auto-reset count is only incremented when the trip is the same as the previous trip otherwise it is reset to 0. When the auto-reset count
reaches the programmed value, any further trip of the same value will not cause an auto-reset. If there has been no trip for 5 minutes then the auto-reset count is
cleared. Auto reset will not occur after any trips with priority levels 1, 2 or 3 as defined in the Trips section of this guide. When a manual reset occurs the auto-reset
counter is reset to zero.
If NumberOfAuto-resetAttempts (10.034) = 6 the auto-reset counter is held at zero, and so there is no limit on the number of auto-reset attempts.
Parameter 10.035  Auto-reset Delay
Short description Set to the required auto-reset delay
Mode Open‑loop
Minimum 1.0 Maximum 600.0
Default 1.0 Units s
Type 16 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 1
Coding RW, BU
See NumberOfAuto-resetAttempts (10.034).
Parameter 10.036  Auto-reset Hold Drive Healthy
Short description Set to hold drive healthy if futher auto-reset attempts are possible
Mode Open‑loop
Minimum 0 Maximum 1
Default 0 Units  
Type 1 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 0
Coding RW
If Auto-resetHoldDriveHealthy (10.036) = 0 then DriveHealthy (10.001) is cleared every time the drive trips regardless of any auto-reset that may occur. If Auto-
resetHoldDriveHealthy (10.036) = 1 then DriveHealthy (10.001)  is not cleared on a trip if any further auto-reset attempts are possible. Note that if the under
voltage state becomes active DriveHealthy (10.001) is always set to zero.
Parameter 10.037  Action On Trip Detection
Short description Defines the action of the drive on detection of a trip
Mode Open‑loop
Minimum
0
(Display: 00000)
Maximum
31
(Display: 11111)
Default
0
(Display: 00000)
Units  
Type 8 Bit User Save Update Rate Background read
Display Format Binary Decimal Places 0
Coding RW
The bits in ActionOnTripDetection (10.037) are defined as follows:
Bit 0: Stop on defined non-important trips
If bit 0 is set to one the drive will attempt to stop before tripping if any of the following trip conditions are detected: I/OOverload, KeypadMode, MotorTooHot,
EEPROMFail or user 24V failure.
Bit 1: Braking resistor overload detection
0 = trip, 1 = Disable brake IGBT.
See BrakingResistorRatedPower (10.030).
Bit 2: Disable phase loss stop
Normally the drive will stop when the input phase loss condition is detected. If this bit is set to 1 the drive will continue to run and will only trip when the drive is
brought to a stop by the user.
Bit 4: Disable parameter freeze on trip
If this bit is 0 then the parameters listed below are frozen on trip until the trip is cleared. If this bit is 1 then this feature is disabled.
ReferenceSelected (01.001)
Pre-skipFilterReference (01.002)
Pre-rampReference (01.003)
FrequencyReference (03.045)
FinalDemandReference (03.001)
CurrentMagnitude (04.001)
TorqueProducingCurrent (04.002)
MagnetisingCurrent (04.017)
OutputFrequency (05.001)
OutputVoltage (05.002)
OutputPower (05.003)
D.c.LinkVoltage (05.005)
AnalogInput1 (07.001)
AnalogInput2 (07.002)
Because of the limited number of segments on drives with an LED display, these drives will indicate the parameter value as a
decimal value rather than a binary value.