Menu 12 − User Functions 2 and Brake Control
Mode: Open‑loop
Menu 12 provides parameters for the following features:
1.  Threshold detectors
2.  Variable selectors
3.  Mechanical brake controller
Parameter 12.001  Threshold Detector 1 Output
Short description Displays the output of threshold detector 1
Mode Open‑loop
Minimum 0 Maximum 1
Default   Units  
Type 1 Bit Volatile Update Rate 4ms write
Display Format Standard Decimal Places 0
Coding RO, ND, NC, PT
The threshold detector functions are always active even if the source and destination are not routed to valid parameters. If the source is not a valid parameter then the source value is taken as 0. The
update rate for each of the threshold detector functions is always 4ms.
The following description is for threshold detector 1, but threshold detector 2 operates in the same way. The level of the parameter defined by ThresholdDetector1Source (12.003) is converted to a
percentage and compared to ThresholdDetector1Level (12.004) with hysteresis to give ThresholdDetector1Output (12.001) as follows:
Source Threshold Detector 1 Output (12.001)
Source < Lower threshold 0
Lower threshold ≤ Source < Upper threshold No change of state
Source ≥ Upper threshold 1
Lower threshold = ThresholdDetector1Level (12.004) - (ThresholdDetector1Hysteresis (12.005) / 2)
Upper threshold = ThresholdDetector1Level (12.004) + (ThresholdDetector1Hysteresis (12.005) / 2)
The output value can then be inverted with ThresholdDetector1OutputInvert (12.006) before being routed to the destination defined by ThresholdDetector1Destination (12.007).
Parameter 12.002  Threshold Detector 2 Output
Short description Displays the output of threshold detector 2
Mode Open‑loop
Minimum 0 Maximum 1
Default   Units  
Type 1 Bit Volatile Update Rate 4ms write
Display Format Standard Decimal Places 0
Coding RO, ND, NC, PT
See ThresholdDetector1Output (12.001).
Parameter 12.003  Threshold Detector 1 Source
Short description Defines the source paramter for threshold detector 1
Mode Open‑loop
Minimum 0.000 Maximum 30.999
Default 0.000 Units  
Type 16 Bit User Save Update Rate Drive reset read
Display Format Standard Decimal Places 3
Coding RW, PT, BU
See ThresholdDetector1Output (12.001).
Parameter 12.004  Threshold Detector 1 Level
Short description Defines the reference level for threshold detector 1
Mode Open‑loop
Minimum 0.00 Maximum 100.00
Default 0.00 Units %
Type 16 Bit User Save Update Rate 4ms read
Display Format Standard Decimal Places 2
Coding RW
See ThresholdDetector1Output (12.001).