shown as bits in EnableConditions (06.010) as given in the table below.
Enable Conditions
(06.010) bits
Enable condition
0 HardwareEnable (06.029)
1 DriveEnable (06.015)
2 0 if auto tune completed or trip during auto-tune, but drive needs to be disabled and re-enabled
3 Reserved
4 Reserved
5 Zero until the drive thermal model has obtained temperatures from all drive thermistors at least once
6
Zero until all option modules that are present in the drive have indicated that they are ready to run or the system
has timed out waiting for this.
7 Reserved
8-10 Reserved
11 Zero if the drive is in standby mode. See StandbyModeEnable (06.060)
Because of the limited number of segments on drives with an LED display, these drives will indicate the parameter value as a decimal value rather
than a binary value.
Parameter 06.011 Sequencer State Machine Inputs
Short description Displays the states of inputs into the sequencer state machine
Mode Openloop
Minimum
0
(Display: 0000000)
Maximum
127
(Display: 1111111)
Default Units
Type 8 Bit Volatile Update Rate 4ms
Display Format Binary Decimal Places 0
Coding RO, ND, NC, PT, BU
The bits in SequencerStateMachineInputs (06.011) show the state of the inputs to the sequencer state machine as given in the tables below:
Sequencer State Machine Inputs (06.011) bits Signal Indicates
0 Final drive enable The drive inverter is allowed to be enabled.
1 Final drive run The motor can move away from standstill.
2 UnderVoltageActive (10.016) The under voltage condition has been detected.
3 ZeroFrequency (10.003) Indicated when the motor has stopped.
4 Drive tripped The drive is tripped.
5 Limitswitchactive (10.066) Limit switch is active
6 SupplyLoss (10.015) Supply loss condition has been detected.
Because of the limited number of segments on drives with an LED display, these drives will indicate the parameter value as a decimal value rather
than a binary value.
Parameter 06.012 Enable Stop Key
Short description Set to 1 to enable the use of the stop key
Mode Openloop
Minimum 0 Maximum 1
Default 0 Units
Type 1 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 0
Coding RW
The Stop key can be used to stop the drive if EnableStopKey (06.012) = 1 or Keypad command is selected (see ReferenceSelector (01.014)).
If EnableStopKey (06.012)= 0 and Keypad command is not selected. The Stop key is not active and can be used to initiate a drive reset without stopping the drive from running.
If EnableStopKey (06.012) = 1 or Keypad command is selected, the drive reset can be initiated without stopping the drive by holding the Run key and then pressing the Stop key.
The Stop key is also used to reset the drive from the keypad.
It should be noted that if the drive is tripped and is then reset from any source other than the keypad Stop key then the drive may start immediately under the following conditions:
1. EnableSequencerLatching (06.040) = 0, the Final drive enable is active and one of the sequencer bits (RunForward (06.030), RunReverse (06.032) or Run (06.034) is active.
2. EnableSequencerLatching (06.040) = 1, the Final drive enable is active, NotStop (06.039) is active and one of the sequencer bits (RunForward (06.030), RunReverse (06.032) or
Run (06.034) is active.
The drive sequencer has been designed so that pressing the Stop key, whatever the value of EnableStopKey (06.012) or the Command Selection, does not make the drive state change from
stopped to running. As pressing the Stop key could reset a drive trip which could then restart the drive, the run output from the sequencer is held off until the following conditions are met when
the drive is tripped and the Stop key is pressed.
1. RunForward (06.030) = 0 and RunReverse (06.032) = 0 and Run (06.034) = 0*
2. OR RunForward (06.030) = 1 and RunReverse (06.032) = 1 for at least 60ms*
3. OR The Final drive enable = 0
4. OR The sequencer is in the UNDER_VOLTAGE state
5. OR If EnableSequencerLatching (06.040) = 1, NotStop (06.039) = 0
* If EnableSequencerLatching (06.040) = 1 then the state of these sequencer bits must be 0 at the output of their latches.
Once the necessary conditions have been met the drive can then be restarted by activating the necessary bits for a normal start.
Parameter 06.013 Enable Auxiliary Key
Short description Defines the behaviour of the drive when the auxilliary button is pressed
Mode Openloop
Minimum 0 Maximum 2
Default 0 Units
Type 8 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 0
Coding RW, TE
88
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10