Parameter 09.048 Timer 2 Stop Time
Short description Defines the stop time for timer 2
Mode Openloop
Minimum
0
(Display: 00:00:00)
Maximum
235959
(Display: 23:59:59)
Default
0
(Display: 00:00:00)
Units
Type 32 Bit User Save Update Rate Background read
Display Format Time Decimal Places 0
Coding RW
Timer2StopTime (09.048) defines the stop time within the repeat period of timer 2.
See Timer1RepeatFunction (09.039) for more information.
Parameter 09.049 Timer 2 Repeat Function
Short description Defines the length of the repeat period
Mode Openloop
Minimum 0 Maximum 7
Default 0 Units
Type 8 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 0
Coding RW, TE
Value Text
0 None
1 1
2 2
3 3
4 4
5 5
6 6
7 7
See Timer1RepeatFunction (09.039).
Parameter 09.050 Timer 2 Enable
Short description Set to enable the timer 2 function
Mode Openloop
Minimum 0 Maximum 1
Default 0 Units
Type 1 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 0
Coding RW
Timer2Enable (09.050) enables the timer 2 function. If Timer2Enable (09.050) = 0, then the output of the timer is always inactive, i.e. Timer2Output
(09.052) = 0.
Parameter 09.051 Timer 2 Invert
Short description Set to invert the output of timer 2
Mode Openloop
Minimum 0 Maximum 1
Default 0 Units
Type 1 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 0
Coding RW
Timer2Invert (09.051) inverts the timer output to give an active state of 0 instead of 1.
See Timer1Invert (09.041) for more information.
Parameter 09.052 Timer 2 Output
Short description Shows the output state of timer function 2
Mode Openloop
Minimum 0 Maximum 1
Default Units
Type 1 Bit Volatile Update Rate Background write
Display Format Standard Decimal Places 0
Coding RO, ND, NC, PT
Unidrive M200 Parameter Reference Guide