LogicFunction1Source1 (09.004) defines input souce 1 of logic function 1.
Parameter 09.005 Logic Function 1 Source 1 Invert
Short description Set to invert input 1 of logic function 1
Mode Openloop
Minimum 0 Maximum 1
Default 0 Units
Type 1 Bit User Save Update Rate 4ms read
Display Format Standard Decimal Places 0
Coding RW
Setting LogicFunction1Source1Invert (09.005) inverts input 1 of logic function 1.
Parameter 09.006 Logic Function 1 Source 2
Short description Defines input source 2 of logic function 1
Mode Openloop
Minimum 0.000 Maximum 30.999
Default 0.000 Units
Type 16 Bit User Save Update Rate Drive reset read
Display Format Standard Decimal Places 3
Coding RW, PT, BU
LogicFunction1Source2 (09.006) defines input source 2 of logic function 1.
Parameter 09.007 Logic Function 1 Source 2 Invert
Short description Set to invert input 2 of logic function 1
Mode Openloop
Minimum 0 Maximum 1
Default 0 Units
Type 1 Bit User Save Update Rate 4ms read
Display Format Standard Decimal Places 0
Coding RW
Setting LogicFunction1Source2Invert (09.007) inverts input 2 of logic function 1.
Parameter 09.008 Logic Function 1 Output Invert
Short description Set to invert the ouptut of logic function 1
Mode Openloop
Minimum 0 Maximum 1
Default 0 Units
Type 1 Bit User Save Update Rate 4ms read
Display Format Standard Decimal Places 0
Coding RW
Setting LogicFunction1OutputInvert (09.008) inverts the output of logic function 1.
Parameter 09.009 Logic Function 1 Delay
Short description Defines the output delay of logic function 1
Mode Openloop
Minimum -25.0 Maximum 25.0
Default 0.0 Units s
Type 16 Bit User Save Update Rate 4ms read
Display Format Standard Decimal Places 1
Coding RW
LogicFunction1Delay (09.009) defines the delay at the output of logic function 1. If LogicFunction1Delay (09.009) is positive then the output does not
become 1 until the input to the delay has been at 1 for the delay time. If LogicFunction1Delay (09.009) is negative then the output remains at 1 until
the input to the delay has been 0 for the delay time.
130
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10