Parameter 06.023 Time Before Filter Change Due
Short description Displays the time before a filter change is required
Mode Openloop
Minimum 0 Maximum 30000
Default Units Hours
Type 16 Bit Power Down Save Update Rate Background write
Display Format Standard Decimal Places 0
Coding RO, ND, NC, PT
See TimeBetweenFilterChanges (06.021).
Parameter 06.024 Reset Energy Meter
Short description Set to 1 to reset the energy meter
Mode Openloop
Minimum 0 Maximum 1
Default 0 Units
Type 1 Bit Volatile Update Rate Background read
Display Format Standard Decimal Places 0
Coding RW
EnergyMeter:MWh (06.025) and EnergyMeter:kWh (06.026) accumulate the energy transferred through the drive. A positive energy value indicates net transfer of energy from the drive to the
motor. If ResetEnergyMeter (06.024) = 1 then EnergyMeter:MWh (06.025) and EnergyMeter:kWh (06.026) are held at zero. If ResetEnergyMeter (06.024) = 0 then the energy meter is
enabled and will accumulate the energy flow. If the maximum or minimum of EnergyMeter:MWh (06.025) is reached the parameter does not rollover and is instead clamped at the maximum or
minimum value.
Parameter 06.025 Energy Meter: MWh
Short description Displays the energy accumulated by through the drive in MWh
Mode Openloop
Minimum -999.9 Maximum 999.9
Default Units MWh
Type 16 Bit Power Down Save Update Rate Background write
Display Format Standard Decimal Places 1
Coding RO, ND, NC, PT
See ResetEnergyMeter (06.024).
Parameter 06.026 Energy Meter: kWh
Short description Displays the energy accumulated by through the drive in kWh
Mode Openloop
Minimum -99.99 Maximum 99.99
Default Units kWh
Type 16 Bit Power Down Save Update Rate Background write
Display Format Standard Decimal Places 2
Coding RO, ND, NC, PT
See ResetEnergyMeter (06.024).
Parameter 06.027 Energy Cost Per kWh
Short description Defines the cost of energy per kWh
Mode Openloop
Minimum 0.0 Maximum 600.0
Default 0.0 Units
Type 16 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 1
Coding RW
RunningCost (06.028) is derived from the OutputPower (05.003) and the EnergyCostPerkWh (06.027) in cost per hour. The sign of RunningCost (06.028) is the same as the sign of
OutputPower (05.003).
Parameter 06.028 Running Cost
Short description Displays the running cost of the drive
Mode Openloop
Minimum -32000 Maximum 32000
Default Units
Type 16 Bit Volatile Update Rate Background write
Display Format Standard Decimal Places 0
Coding RO, ND, NC, PT
See EnergyCostPerkWh (06.027).
Parameter 06.029 Hardware Enable
Short description Set to 1 to enable the hardware of the drive
Mode Openloop
Minimum 0 Maximum 1
Default Units
Type 1 Bit Volatile Update Rate 4ms
Display Format Standard Decimal Places 0
Coding RO, ND, NC, PT, BU
HardwareEnable (06.029) shows the hardware enable state. Drive I/O is routed to UserEnable (06.038). See description of the enable logic for more details.
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10