VM_SPEED_FREQ_REF_UNIPOLAR[MIN] = 0.00
Identifier VM_SPEED_FREQ_USER_REFS
Description Range applied to analogue reference parameters
Units Hz
Range of [MIN] -550.00 to 550.00
Range of [MAX] 0.00 to 550.00
This variable maximum is applied to AnalogueReference1 (01.036), AnalogueReference2 (01.037) and KeypadReference (01.017).
The maximum applied to these parameters is the same as other frequency reference parameters.
VM_SPEED_FREQ_USER_REFS [MAX] = VM_SPEED_FREQ_REF[MAX]
However the minimum is dependent on NegativeReferenceClampEnable (01.008) and BipolarReferenceEnable (01.010).
Negative Reference
Clamp Enable
(01.008)
Bipolar
Reference
Enable (01.010)
VM_SPEED_FREQ_USER_REFS[MIN]
0 0
If SelectMotor2Parameters (11.045) = 0 MinimumReference
Clamp (01.007), otherwise M2MinimumReferenceClamp (21.002)
0 1 -VM_SPEED_FREQ_REF[MAX]
1 0 0.00
1 1 -VM_SPEED_FREQ_REF[MAX]
Note - Parameter 11.045 is not available on M100/M101 and so only the Motor 1 parameters are relevant.
Identifier VM_SUPPLY_LOSS_LEVEL
Description Range applied to the supply loss threshold
Units V
Range of [MIN] 0 to 1150
Range of [MAX] 0 to 1150
VM_SUPPLY_LOSS_LEVEL[MAX] = VM_DC_VOLTAGE_SET[MAX]
VM_SUPPLY_LOSS_LEVEL[MIN] is drive voltage rating dependent. See the table below.
Voltage level 200V 400V 575V (1) 690V (2)
VM_SUPPLY_LOSS_LEVEL[MIN] 205 410 540 540
(1) Unidrive M frame size 5 and above only
(2) Unidribe M frame size 7 and above only
Identifier VM_TORQUE_CURRENT
Description Range applied to torque and torque producing current parameters.
Units %
Range of [MIN] -1000.0 to 0.0
Range of [MAX]
0.0 to 1000.0
Select Motor 2 Parameters
(11.045)
VM_TORQUE_CURRENT[MAX]
0 VM_MOTOR1_CURRENT_LIMIT[MAX]
1 VM_MOTOR2_CURRENT_LIMIT[MAX]
VM_TORQUE_CURRENT[MIN] = -VM_TORQUE_CURRENT[MAX]
Identifier VM_TORQUE_CURRENT_UNIPOLAR
Description Unipolar version of VM_TORQUE_CURRENT
Units %
Range of [MIN] 0.0
Range of [MAX] 0.0 to 1000.0
VM_TORQUE_CURRENT_UNIPOLAR[MAX] = VM_TORQUE_CURRENT[MAX]
VM_TORQUE_CURRENT_UNIPOLAR[MIN] =0.0