Parameter 10.001 Drive Healthy
Short description Indicates that the drive is healthy
Mode Open‑loop
Minimum 0 Maximum 1
Default Units
Type 1 Bit Volatile Update Rate Background write
Display Format Standard Decimal Places 0
Coding RO, ND, NC, PT
DriveHealthy (10.001) indicates that the drive is not in the trip or the under voltage state if it is set to one. If Auto-resetHoldDriveHealthy (10.036) = 1 and auto-
reset is being used, DriveHealthy (10.001) is not cleared until all auto-resets have been attempted and the next trip occurs.
Parameter 10.002 Drive Active
Short description Indicates that the inverter is active
Mode Open‑loop
Minimum 0 Maximum 1
Default Units
Type 1 Bit Volatile Update Rate Background write
Display Format Standard Decimal Places 0
Coding RO, ND, NC, PT
If the drive inverter is active DriveActive (10.002) is set to one, otherwise it is zero.
Parameter 10.003 Zero Frequency
Short description Indicates that the frequency is below the zero frequency threshold
Mode Open‑loop
Minimum 0 Maximum 1
Default Units
Type 1 Bit Volatile Update Rate Background write
Display Format Standard Decimal Places 0
Coding RO, ND, NC, PT
ZeroFrequency (10.003) is set to one under the zero frequency conditions, otherwise it is zero. See ZeroFrequencyThreshold (03.005).
Parameter 10.004 Running At Or Below Minimum Frequency
Short description Indicates that the drive is running at or below the minimum frequency
Mode Open‑loop
Minimum 0 Maximum 1
Default Units
Type 1 Bit Volatile Update Rate Background write
Display Format Standard Decimal Places 0
Coding RO, ND, NC, PT
If BipolarReferenceEnable (01.010) = 1 then RunningAtOrBelowMinimumFrequency (10.004) operates in the same way as ZeroFrequency (10.003). If
BipolarReferenceEnable (01.010) = 0 then RunningAtOrBelowMinimumFrequency (10.004) is set if PostRampReference (02.001) ≤ MinimumSpeed (01.007) +
0.5Hz.
If motor map 2 is active then M2MinimumSpeed (21.002) is used instead of MinimumSpeed (01.007).
Parameter 10.005 Below Set Frequency
Short description Indicates that the drive is running below the set frequency
Mode Open‑loop
Minimum 0 Maximum 1
Default Units
Type 1 Bit Volatile Update Rate Background write
Display Format Standard Decimal Places 0
Coding RO, ND, NC, PT
See AtFrequencyLowerLimit (03.006).
Parameter 10.006 At Frequency
Short description Indicates that the drive is running at the set frequency
Mode Open‑loop
Minimum 0 Maximum 1
Default Units
Type 1 Bit Volatile Update Rate Background write
Display Format Standard Decimal Places 0
Coding RO, ND, NC, PT
See AtFrequencyLowerLimit (03.006).