Value Mode Function
-6 4-20mA Stop 4-20mA with stop on current loop loss
-5 20-4mA Stop 20-4mA with stop on current loop loss
-4 4-20mA Low 4-20mA with switching to a low speed set in AnalogInput1PresetonCurrentLoss (07.026) on current loop loss
-3 20-4mA Low 20-4mA with switching to a low speed set in AnalogInput1PresetonCurrentLoss (07.026) on current loop loss
-2 4-20mA Hold 4-20mA with hold at level before loss on current loop loss (1)
-1 20-4mA Hold 20-4mA with hold at level before loss on current loop loss (1)
0 0-20mA 0-20mA
1 20-0mA 20-0mA
2 4-20mA Trip 4-20mA with AnInput1Loss trip on current loss.
3 20-4mA Trip 20-4mA with AnInput1Loss trip on current loss.
4 4-20mA 4-20mA with no action on current loop loss (input taken as 0%).
5 20-4mA 20-4mA with no action on current loop loss (input taken as 0%).
6 Voltage Voltage input
(1) Analog input level remains at the value it had in the previous sample before the current fell below 3mA.
Parameter 07.008 Analog Input 1 Scaling
Short description Defines the scaling factor of analog input 1
Mode Open‑loop
Minimum 0.000 Maximum 10.000
Default 1.000 Units
Type 16 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 3
Coding RW
See AnalogI/O.
AnalogInput1 (07.001) is modified by AnalogInput1Scaling (07.008), AnalogInput1Offset (07.030) and AnalogInput1Invert (07.009) before it is routed to its destination as follows:
A
1O
= AnalogInput1 (07.001) + AnalogInput1Offset (07.030)
A
1O
is the value after the offset has been applied and is limited between -100.00% and 100.00%
A
1S
= A
1O
x AnalogInput1Scaling (07.008)
A
1S
is the value after the scaling and the offset have been applied and is limited between -100.00% and 100.00%
If AnalogInput1Invert (07.009) = 0 then A
1I
= A
1S
otherwise A
1I
= -A
1S
A1I is the value after the invert, scaling and offset have been applied and is the final value that is routed to the destination defined by
AnalogInput1DestinationA (07.010) if AnalogInput1Control (07.051) = 0
AnalogInput1DestinationB (07.090) if AnalogInput1Control (07.051) > 0
Parameter 07.009 Analog Input 1 Invert
Short description Inverts the signal for analog input 1
Mode Open‑loop
Minimum 0 Maximum 1
Default 0 Units
Type 1 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 0
Coding RW
See AnalogInput1Scaling (07.008).
Parameter 07.010 Analog Input 1 Destination A
Short description Defines the output parameter for analog input 1
Mode Open‑loop
Minimum 0.000 Maximum 30.999
Default 1.036 Units
Type 16 Bit User Save Update Rate Drive reset read
Display Format Standard Decimal Places 3
Coding RW, DE, PT
See AnalogInput1Scaling (07.008).
Parameter 07.011 Analog Input 2 Mode
Short description Defines the mode for analog input 2
Mode Open‑loop
Minimum 6 Maximum 7
Default 6 Units
Type 8 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 0
Coding RW, TE
Value Text
6 Volt
7 dig
See AnalogInput2 (07.002).
The table below gives all the possible analogue input modes.
Value Mode Function
6 Voltage Voltage
7 Digital Digital