Parameter 06.002 Limit Switch Stop Mode
Short description Defines the behaviour of the drive when limit switch is active
Mode Openloop
Minimum 0 Maximum 1
Default 1 Units
Type 8 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 0
Coding RW, TE
Value Text
0 Stop
1 rp
If LimitSwitchStopMode (06.002) = 0 then when Limitswitchactive (10.066) is activated the motor is stopped without ramps (under dc injection control).
If LimitSwitchStopMode (06.002) = 1 then the motor is stopped with the currently selected ramp rate.
Parameter 06.003 Supply Loss Mode
Short description Defines the behaviour of the drive when the supply voltage is reduced
Mode Openloop
Minimum 0 Maximum 3
Default 0 Units
Type 8 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 0
Coding RW, TE
Value Text Description
0 diS Disabled
1 rP.Stop Ramp Stop
2 ridE.th Ride through
3 Lt.Stop Limit Stop
If SupplyLossMode (06.003) > 0 and the D.c.LinkVoltage (05.005) falls below SupplyLossDetectionLevel (06.048) then the supply loss condition is detected. If SupplyLossMode (06.003) =
2 (ride through) the supply loss system will attempt to control the D.c.LinkVoltage (05.005) to a level just below the SupplyLossDetectionLevel (06.048) using a d.c. link voltage controller
which provides a torque producing current reference to the current controllers to regulate the power flow into the d.c. link. Therefore CurrentControllerKpGain (04.013) and
CurrentControllerKiGain (04.014) must be set up correctly for the application. When the supply is reapplied it must be at a level that is high enough for the D.c.LinkVoltage (05.005) to rise
above SupplyLossDetectionLevel (06.048) plus a hysteresis margin. This will disable the supply loss controller and the drive will return to normal operation. The table below gives the d.c. link
voltage levels used by the supply loss detection system for different drive voltage ratings.
Voltage level 200V 400V 575V 690V
Supply loss d.c. link voltage control level
SupplyLossDetectionLevel
(06.048) - 10V
SupplyLossDetectionLevel
(06.048) - 20V
SupplyLossDetectionLevel
(06.048) - 25V
SupplyLossDetectionLevel
(06.048) - 25V
Voltage above which supply loss detection changes
from active to inactive
SupplyLossDetectionLevel
(06.048) +10V
SupplyLossDetectionLevel
(06.048) + 15V
SupplyLossDetectionLevel
(06.048) + 50V
SupplyLossDetectionLevel
(06.048) + 50V
0: Disable
No supply loss detection is provided by monitoring the D.c.LinkVoltage (05.005). The drive will continue to operate normally unless the under voltage condition is detected.
1: Ramp Stop
The action taken by the drive is the same as for ride through mode, except that the ramp down rate is at least as fast as the currently selected deceleration ramp and the drive will continue to
decelerate and stop even if the supply is re-applied. If StopMode (06.001) = 3 or 4 (i.e. d.c. injection) the drive will use ramp mode to stop on loss of the supply. If StopMode (06.001) = 2 (i.e.
ramp stop followed by injection) the drive will ramp to a stop and then attempt to apply d.c. injection. The ramp down rate is at least as fast as the currently selected deceleration ramp and the
drive will continue to decelerate and stop even if the supply is re-applied. Once the sequencer state machine has reached the DISABLE state the drive can restart provided the necessary
controls are still active to initiate a start.
2: Ride through
The drive attempts to control the d.c. link voltage to take energy from the motor and load inertia to ride through the Supply loss condition for as long as possible.
Parameter 06.004 Start/Stop Logic Select
Short description Used to select the logic function of the drive input terminals
Mode Openloop
Minimum 0 Maximum 6
Default 0 Units
Type 8 Bit User Save Update Rate
Actioned on exit of edit mode and on
drive reset
Display Format Standard Decimal Places 0
Coding RW
This parameter changes the functions of the input terminals which are normally associated with the enabling, starting and stopping the drive. This also writes to EnableSequencerLatching
(06.040) to enable and disable the input latches.
Start/Stop Logic Select
(06.004)
Digital I/O 2 (M100 - M201)
Terminal 11
Digital I/O 2 (M300- M400)
Terminal 11
Digital Input 3
Terminal 12
Digital Input 4
Terminal 13
EnableSequencerLatching
(06.040)
0 (default) User Enable Undefined Run Forward Run Reverse 0 (non-latching)
1 Not Stop Not Stop Run Forward Run Reverse 1 (latching)
2 User Enable Undefined Run Reverse 0 (non-latching)
3 Not Stop Not Stop Run Reverse 1 (latching)
4 Not Stop Not Stop Run Jog Forward 1 (latching)
5 User programmable User programmable Run Forward Run Reverse 0 (non-latching)
6 User programmable User programmable User programmable User programmable User programmable
86