Parameter 08.062 Keypad Auxiliary Button Destination
Short description Defines the destination parameter for digital input 12
Mode Open‑loop
Minimum 0.000 Maximum 30.999
Default 0.000 Units
Type 16 Bit User Save Update Rate Drive reset read
Display Format Standard Decimal Places 3
Coding RW, DE, PT
This destination parameter provides the routing for the Keypad Auxiliary (DI 12) input, see KeypadAuxiliaryButtonInvert/Toggle (08.052).
The Auxiliary button is available on the remote KI-Keypad.
Parameter 08.063 24V Supply Input Destination
Short description Defines the destination paramter for DI 13
Mode Open‑loop
Minimum 0.000 Maximum 30.999
Default 0.000 Units
Type 16 Bit User Save Update Rate Drive reset read
Display Format Standard Decimal Places 3
Coding RW, DE, PT, BU
This destination parameter provides the routing for the 24V (DI 13) input, see 24VSupplyInputInvert (08.053).
The 24V Input is available on the AI SD card adaptor and the AI 485 Backup adaptor.
Parameter 08.081 DI1 Control
Short description Defines the behaviour of digital input 1
Mode Open‑loop
Minimum 0 Maximum 26
Default 0 Units
Type 8 Bit User Save Update Rate Drive reset read
Display Format Standard Decimal Places 0
Coding RW
Value Description DI/O xx Source/Destination B Other setup
0 User defined by DigitalIO1Source/DestinationA (08.021) to DigitalInput05DestinationA (08.025) 00.000
1 Multi preset ref selection 1 01.045
2 Multi preset ref selection 2 01.046
3 Multi preset ref selection 3 01.047
4 External stop command 06.039
5 Acc time selection 1 02.032
6 Acc time selection 2 02.033
7 Acc time selection 3 02.034
8 Speed control and torque control switcher 04.011
9 External fault N.C. contact input 10.032
10 External reset 10.033
11 External jog fwd 06.031
12 External jog rev 06.037
13 Drive enable 06.015
14 Ramp hold 02.003
15 RUN FWD 06.030
16 RUN REV 06.032
17 3-line run control (Latching) 06.040
18 Forward limit switch 06.035
19 Reverse limit switch 06.036
20 Main ref channel selection 3 01.043
21 Main ref channel selection 2 01.042
22 Main ref channel selection 3 01.041
23 PID1 Enable 14.008
24 Motor 1/2 switcher 11.045
25 Motorised pot UP 09.026
26 Motorised pot DOWN 09.027
This offers a simple control of DI/O01Source/DestinationB (08.121) to DI05DestinationB (08.125), to change the digital input destination. If DIxControl (08.08x) is ≥ 1 then the destination is defined by DI/O0x
Source/Destination B (08.12x). DI/O0xSource/Destination B (08.12x) is written by DIxControl (08.08x) selection. (e.g. If DI1Control (08.081) = 9 then DI/O01Source/DestinationB (08.121) = 10.032).
If DIxControl (08.08x) is 0 then the destination is defined by DI/O0xSource/Destination A (08.02x).
Parameter 08.082 DI2 Control
Short description Defines the behaviour of digital input 2
Mode Open‑loop
Minimum 0 Maximum 26
Default 0 Units
Type 8 Bit User Save Update Rate Drive reset read
Display Format Standard Decimal Places 0
Coding RW
See DI1Control (08.081).
Parameter 08.083 DI3 Control
Short description Defines the behaviour of digital input 3
Mode Open‑loop
Minimum 0 Maximum 26
Default 0 Units
Type 8 Bit User Save Update Rate Drive reset read
Display Format Standard Decimal Places 0
Coding RW
See DI1Control (08.081).