Parameter 05.040 Spin Start Boost
Short description Defines the level of spin start boost used by the algorithm that detects the speed of a spinning motor
Mode Open‑loop
Minimum 0.0 Maximum 10.0
Default 1.0 Units
Type 8 Bit User Save Update Rate Background write
Display Format Standard Decimal Places 1
Coding RW
SpinStartBoost (05.040) is used by the algorithm that detects the frequency of a spinning motor when the drive is enabled and CatchASpinningMotor
(06.009) ≥ 1. For smaller motors the default value of 1.0 is suitable, but for larger motors SpinStartBoost (05.040) may need to be increased. If
SpinStartBoost (05.040) is too small the drive will detect zero speed whatever the frequency of the motor, and if SpinStartBoost (05.040) is too large the
motor may accelerate away from standstill when the drive is enabled.
Parameter 05.042 Reverse Output Phase Sequence
Short description Set to 1 to reverse the sequence on the output phases
Mode Open‑loop
Minimum 0 Maximum 1
Default 0 Units
Type 1 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 0
Coding RW
If ReverseOutputPhaseSequence (05.042) = 0 the output phase sequence is U-V-W when OutputFrequency (05.001) is positive and W-V-U when
OutputFrequency (05.001) is negative. If ReverseOutputPhaseSequence (05.042) = 1 the output phase sequence is reversed so that the phase sequence
in W-V-U for positive frequencies and U-V-W for negative frequencies.
Parameter 05.059 Maximum Deadtime Compensation
Short description Maximum Deadtime Compensation
Mode Open‑loop
Minimum 0.000 Maximum 10.000
Default 0.000 Units µs
Type 16 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 3
Coding RO, NC, PT
MaximumDeadtimeCompensation (05.059) is the deadtime compensation used to compensate for dead-time effects in the inverter. This level of
compensation is used when the drive output current is above CurrentAtMaximumDeadtimeCompensation (05.060) Both of these values related to dead-
time compensation are measured during auto-tuning and cannot be set by the user. It should be noted that if the auto-tuning test is not performed and
MaximumDeadtimeCompensation (05.059) = 0 then dead-time compensation is disabled. Although it is not recommended, it is possible to disable dead-time
compensation by setting DisableDeadtimeCompensation (05.061) = 1.
Parameter 05.060 Current At Maximum Deadtime Compensation
Short description Current at which maximum deadtime compensation is applied
Mode Open‑loop
Minimum 0.00 Maximum 100.00
Default 0.00 Units %
Type 16 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 2
Coding RO, NC, PT
See MaximumDeadtimeCompensation (05.059).
Parameter 05.061 Disable Deadtime Compensation
Short description Disable Deadtime Compensation
Mode Open‑loop
Minimum 0 Maximum 1
Default 0 Units
Type 1 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 0
Coding RW
See MaximumDeadtimeCompensation (05.059).
Parameter 05.074 Boost End Voltage
Short description Defines the boost end voltage
Mode Open‑loop
Minimum 0.0 Maximum 100.0
Default 50.0 Units %
Type 16 Bit User Save Update Rate 16ms
Display Format Standard Decimal Places 1
Coding RW
See Open-loopVoltageMode (05.014).