Parameter 08.025 Digital Input 05 Destination A
Short description Defines the destination parameter for Digital Input 5
Mode Open‑loop
Minimum 0.000 Maximum 30.999
Default 1.041 Units
Type 16 Bit User Save Update Rate Drive reset read
Display Format Standard Decimal Places 3
Coding RW, DE, PT
DigitalInput05DestinationA (08.025) provides the destination parameter if DI5Control (08.085) is at its default value of 0.
Parameter 08.028 Relay 1 Output Source A
Short description Defines the source parameter for relay 1
Mode Open‑loop
Minimum 0.000 Maximum 30.999
Default 10.001 Units
Type 16 Bit User Save Update Rate Drive reset read
Display Format Standard Decimal Places 3
Coding RW, PT
Relay1OutputSourceA (08.028) provides the source parameter if Relay1Control (08.098) is at its default value of 0.
Parameter 08.031 Digital I/O 01 mode
Short description Defines the mode for the functionality of digital input/output 1
Mode Open‑loop
Minimum 0 Maximum 3
Default 1 Units
Type 8 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 0
Coding RW, TE
Value Text Description
0 Input Digital input
1 Output Digital output
2 FR Frequency output
3 Pulse PWM output
This parameter selects the function of input/output DI/O 1.
See also DigitalI/O1State (08.001).
Parameter 08.035 Digital input 5 mode
Short description Defines the function for digital input 5
Mode Open‑loop
Minimum 0 Maximum 4
Default 0 Units
Type 8 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 0
Coding RW, TE
Value Text Description
0 Input Input
1 Th.Sct
Temperature measurement input with short circuit detection
(Resistance <50Ohm)
2 th
Temperature measurement input with Thermistor trip, but
without short circuit detection
3 Th.NoTr Temperature measurement input with no trips
4 FR Frequency Input
This parameter selects the function of input DI 05.
For digital input operation see DigitalInput5State (08.005).
For operation as a thermistor input see ThermistorType (07.046) and ThermistorFeedback (07.047).
The motor thermistor should be connected between terminal 14 and terminal 1 (0 V).
For operation as a frequency input see Position (03.029).
Parameter 08.041 Keypad Run Button State
Short description Displays the state for the Keypad Run Forward button
Mode Open‑loop
Minimum 0 Maximum 1
Default Units
Type 1 Bit Volatile Update Rate Background read
Display Format Standard Decimal Places 0
Coding RO, ND, NC, PT
Digital Input 11 (Keypad Run Button), Digital Input 12 (Keypad Auxiliary Button) and Digital Input 14 (Keypad Stop Button) represent the state of the Run, Auxiliary and Stop buttons on any keypad fitted or
connected to the drive; the input state is determined by OR'ing the state of the button on each keypad connected to the drive, if the button is pressed the state parameter is one otherwise it is zero. If a keypad is
not fitted the state parameters are zero.
Parameter 08.042 Keypad Auxiliary Button State
Short description Displays the state for the Keypad Auxilary button
Mode Open‑loop
Minimum 0 Maximum 1
Default Units
Type 1 Bit Volatile Update Rate Background read
Display Format Standard Decimal Places 0
Coding RO, ND, NC, PT
See KeypadRunButtonState (08.041).