Parameter 09.025 Motorised Pot Destination
Short description Defines the output destination of the motorised pot
Mode Open‑loop
Minimum 0.000 Maximum 30.999
Default 0.000 Units
Type 16 Bit User Save Update Rate Drive reset read
Display Format Standard Decimal Places 3
Coding RW, DE, PT, BU
MotorisedPotDestination (09.025) defines the output destination of the motorised pot function.
Parameter 09.026 Motorised Pot Up
Short description Set to increase the motorised pot output
Mode Open‑loop
Minimum 0 Maximum 1
Default 0 Units
Type 1 Bit Volatile Update Rate 4ms read
Display Format Standard Decimal Places 0
Coding RW, NC
If MotorisedPotUp (09.026) = 1, then the MotorisedPotOutput (09.003) will increase.
Parameter 09.027 Motorised Pot Down
Short description Set to decrese the motorised pot output
Mode Open‑loop
Minimum 0 Maximum 1
Default 0 Units
Type 1 Bit Volatile Update Rate 4ms read
Display Format Standard Decimal Places 0
Coding RW, NC
If MotorisedPotDown (09.027) = 1 and MotorisedPotUp (09.026) = 0 , then the MotorisedPotOutput (09.003) will decrease.
Parameter 09.028 Motorised Pot Reset
Short description Set to reset the motorised pot output to zero
Mode Open‑loop
Minimum 0 Maximum 1
Default 0 Units
Type 1 Bit Volatile Update Rate 4ms read
Display Format Standard Decimal Places 0
Coding RW, NC
If MotorisedPotReset (09.028) = 1 then the motorised pot is disabled and held in its reset state with MotorisedPotOutput (09.003) = 0.0%.
If MotorisedPotReset (09.028) the motorised pot is enabled even if MotorisedPotDestination (09.025) is not routed to a valid parameter.
Parameter 09.029 Binary Sum Ones
Short description Set to add one to the binary sum output
Mode Open‑loop
Minimum 0 Maximum 1
Default 0 Units
Type 1 Bit Volatile Update Rate 4ms read
Display Format Standard Decimal Places 0
Coding RW
See BinarySumOutput (09.032).
Parameter 09.030 Binary Sum Twos
Short description Set to add two to the binary sum output
Mode Open‑loop
Minimum 0 Maximum 1
Default 0 Units
Type 1 Bit Volatile Update Rate 4ms read
Display Format Standard Decimal Places 0
Coding RW
See BinarySumOutput (09.032).