Parameter 08.084 DI4 Control
Short description Defines the behaviour of digital input 4
Mode Openloop
Minimum 0 Maximum 26
Default 0 Units
Type 8 Bit User Save Update Rate Drive reset read
Display Format Standard Decimal Places 0
Coding RW
See DI1Control (08.081).
Parameter 08.085 DI5 Control
Short description Defines the behaviour of digital input 5
Mode Openloop
Minimum 0 Maximum 26
Default 0 Units
Type 8 Bit User Save Update Rate Drive reset read
Display Format Standard Decimal Places 0
Coding RW
See DI1Control (08.081).
Parameter 08.091 DO1 Control
Short description Defines the behaviour of digital output 1
Mode Openloop
Minimum 0 Maximum 21
Default 0 Units
Type 8 Bit User Save Update Rate Drive reset read
Display Format Standard Decimal Places 0
Coding RW
Value Description DI/O 01 Source/Destination B (08.121) or Relay 01 Source B (08.128)
0 User defined by DigitalIO1Source/DestinationA (08.021) or Relay1OutputSourceA (08.028) 00.000
1 Drive running signal (RUN) 10.002
2 Frequency arrived signal (FAR) 10.006 (at frequency)
3 Reserved Reserved
4 Reserved Reserved
5 Overload detection signal (OL) 10.017
6 Power off state (LU) 10.016
7 External fault stop (EXT) 10.032
8 Frequency upper limit (FHL) 10.007
9 Frequency lower limit (FLL) 10.004
10 Drive running at zero frequency 10.003
11 Reserved Reserved
12 Reserved Reserved
13 Reserved Reserved
14 Drive (RDY) 10.090
15 Drive healthy 10.001
16 Reserved Reserved
17 Reserved Reserved
18 Brake release 12.040
19
Torque limiting
(Valid while the torque is limited by torque limiting value 1/2)
10.009
20 Forward or reverse 10.014
21 Motor 1 or 2 11.045
This offers a simple control of parameter DI/O01Source/DestinationB (08.121) or Relay01SourceB (08.128) to change the source.
If the control parameter (08.09x) is more than 0 then the source is defined by the relevant source parameter B (08.12x). The source parameter is written by the control selection. (e.g. If DO1Control (08.091) = 10
then DI/O01Source/DestinationB (08.121) = 10.003)
If the control parameter is 0 then the source is defined by the relevant source parameter A (08.02x).
Parameter 08.098 Relay 1 Control
Short description Defines the behaviour of relay 1
Mode Openloop
Minimum 0 Maximum 21
Default 0 Units
Type 8 Bit User Save Update Rate Action on exit from edit and reset
Display Format Standard Decimal Places 0
Coding RW
See DO1Control (08.091).
Parameter 08.121 DI/O 01 Source/Destination B
Short description Defines the secondary source or destination parameter for digital input/output 1
Mode Openloop
Minimum 0.000 Maximum 30.999
Default Units
Type 16 Bit User Save Update Rate Drive reset read
Display Format Standard Decimal Places 3
Coding RO, DE, ND, NC, PT
Refer to control parameters ( DI1Control (08.081) and DO1Control (08.091)) for more information.
Parameter 08.122 DI/O 02 Source/Destination B
Short description Defines the secondary source or destination parameter for digital input/output 2
Mode Openloop
Minimum 0.000 Maximum 30.999
Default Units
Type 16 Bit User Save Update Rate Drive reset read
Display Format Standard Decimal Places 3
Coding RO, DE, ND, NC, PT
Refer to control parameters ( DI1Control (08.081) for more information.
120